Page 15 
1.6.1  Compressor Control
1)  Reach the configured temperature
• If the following conditions are satisfied, the 
compressor ceases operation.
• While calculated frequency(fb) is less than  
minimum limit frequency(FminC).
• When protective time is more than or equal to ten 
minutes.
• When T1 is higher than or equal to Tsc+ 
HDIFTEMP2.
Note: HDIFTEMP2 is EEPROM setting parameter. It is 2°C 
usually.
• If one of the following conditions is satisfied, not 
judge protective time.
• Compressor running frequency is more than test 
frequency.
• When compressor running frequency is equal to 
test frequency, T4 is more than 15°C or no T4 or T4 
fault. 
• Change setting temperature.
• Turbo or sleep function on/off.
2)  When the current is higher than the predefined safe 
value, surge protection is activated, causing the 
compressor to cease operations.
1.6.2  Indoor Fan Control:
1)  In heating mode, the indoor fan operates continuously. 
The fan speed can be set to 1%-100%, or mute.
2)  Auto fan
• Rise curve
• When T1-Tsc is higher than -1.5°C, fan speed 
reduces to 80%;
• -When T1-Tsc is higher than 0°C, fan speed reduces 
to 60%;
• -When T1-Tsc is higher than 0.5°C, fan speed 
reduces to 40%;
• -When T1-Tsc is higher than 1°C, fan speed reduces 
to 20%.
• Descent curve
• When T1-Tsc is lower than or equal to 0.5°C, fan 
speed increases to 20%;
• -When T1-Tsc is lower than or equal to 0°C, fan 
speed increases to 60%;
• -When T1-Tsc is lower than or equal to -1.5°C, fan 
speed increases to 80%;
• -When T1-Tsc is lower than or equal to -3°C, fan 
speed increases to 100%.
1.6.3  Outdoor Fan Control:
• The outdoor unit will be run at different fan speed 
according to T4 and compressor running frequency.
• For different outdoor units, the fan speeds are 
different.
1.6.4  Defrosting mode 
• The unit enters defrosting mode according to changes 
in the temperature value of T3, T4 as well as the 
compressor running time.
• In defrosting mode, the compressor continues to run, 
the indoor and outdoor motor will cease operation, 
the defrost light of the indoor unit will turn on, and 
the “ ” symbol is displayed.
• If any one of the following conditions is satisfied, 
defrosting ends and the machine switches to normal 
heating mode:
• T3 rises above TCDE1°C.
• T3 maintained above TCDE2°C for 80 seconds.
• Unit runs for 15 minutes consecutively in defrosting 
mode.
1.6.5  Evaporator Temperature Protection
• Off: Compressor stops. 
• Decrease: Decrease the running frequency to the lower 
level per 20 seconds. 
• Hold: Keep the current frequency. 
• Resume: No limitation for frequency.
1.7  Auto-mode
• This mode can be selected with the remote controller 
and the setting temperature can be changed between 
16°C~30°C.
• In auto mode, the machine selects cooling, heating, 
auto-drying or fan-only mode on the basis of T1,Ts, T4 
and relative humidity.
• If the setting temperature is modified, the machine 
selects a new running function.
1.8  Drying mode
In drying mode, AC operates the same as auto fan in 
cooling mode.
1)  Mute function is active.
• All protections are activated and operate the same as 
they do that in cooling mode.
2)  Low Room Temperature Protection
• If the room temperature is lower than 10°C, the 
compressor ceases operations and does not resume