Page 20 
1.  Maintenance
1.1  First Time Installation Check
Air and moisture trapped in the refrigerant system affects 
the performance of the air conditioner by: 
• Increasing pressure in the system.
• Increasing the operating current.
• Decreasing the cooling or heating efficiency.
• Congesting the capillary tubing due to ice build-up in 
the refrigerant circuit.
• Corroding the refrigerant system.
To prevent air and moisture from affecting the air 
conditioner’s performance, the indoor unit, as well as the 
pipes between the indoor and outdoor unit,  must be be 
leak tested and evacuated. 
Leak test (soap water method)
Use a soft brush to apply soapy water or a neutral liquid 
detergent onto the indoor unit connections and outdoor 
unit connections. If there is gas leakage, bubbles will form 
on the connection.
Air purging with vacuum pump