Page 64 
5.4  E3/F5(Fan speed is operating outside of the normal range)
Description: When the indoor fan speed keeps too low (300RPM) or too high (1500RPM) for certain time, the unit will 
stop and the LED will display the failure(E3). When the outdoor fan speed registers below 200RPM or over 1500RPM for 
an extended period of time, the unit will stop and the LED will display the failure(F5).
Recommended parts to prepare:
• Wiring mistake
• Faulty fan assembly
• Faulty fan motor
• Faulty PCB
Troubleshooting and repair:
YES
Power off, then restart the unit after 2 minutes.
Is it within normal parameters?
Replace the fan motor
Does a problem remain?
The unit is operating normallyNO
Shut off the power supply, 
Rotate 
the fan by hand.
YES
Does it turn easily?
Find the cause
 of the problem and 
resolve it
NO
Check the wiring of fan motor. 
YES
Is it improperly wired?
Ensure proper connections
Measure the voltage for  
the fan motor from the  PCB.
YES
Replace the indoor/outdoor  
PCB
NO