Page 4 
• that capacitors are discharged: this shall be done in 
a safe manner to avoid possibility of sparking;
• that there no live electrical components and wiring 
are exposed while charging, recovering or purging 
the system;
• that there is continuity of earth bonding.
2.10  Repairs to sealed components
• During repairs to sealed components, all electrical 
supplies shall be disconnected from the equipment 
being worked upon prior to any removal of sealed 
covers, etc. If it is absolutely necessary to have an 
electrical supply to equipment during servicing, then 
a permanently operating form of leak detection shall 
be located at the most critical point to warn of a 
potentially hazardous situation.
• Particular attention shall be paid to the following to 
ensure that by working on electrical components, the 
casing is not altered in such a way that the level of 
protection is affected. This shall include damage to 
cables, excessive number of connections, terminals 
not made to original specification, damage to seals, 
incorrect fitting of glands, etc.
• Ensure that apparatus is mounted securely.
• Ensure that seals or sealing materials have not 
degraded such that they no longer serve the 
purpose of preventing the ingress of flammable 
atmospheres. Replacement  parts shall be in 
accordance with the manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the 
effectiveness of some types of leak detection equipment. 
Intrinsically safe components do not have to be isolated 
prior to working on them.
2.11  Repair to intrinsically safe components
• Do not apply any permanent inductive or capacitance 
loads to the circuit without ensuring that this will not 
exceed the permissible voltage and current permitted 
for the equipment in use. Intrinsically safe components 
are the only types that can be worked on while live 
in the presence of a flammable atmosphere. The test 
apparatus shall be at the correct rating.
• Replace components only with parts specified by the 
manufacturer. Other parts may result in the ignition of 
refrigerant in the atmosphere from a leak.
2.12  Cabling
• Check that cabling will not be subject to wear, 
corrosion, excessive pressure, vibration, sharp edges 
or any other adverse environmental effects. The check 
shall also take into account the effects of aging or 
continual vibration from sources such as compressors 
or fans.
2.13  Detection of flammable refrigerants
• Under no circumstances shall potential sources of 
ignition be used in the searching for or detection of 
refrigerant leaks. A halide torch (or any other detector 
using a naked flame) shall not be used.
2.14  Leak detection methods
• The following leak detection methods are deemed 
acceptable for systems containing flammable 
refrigerants. Electronic leak detectors shall be used 
to detect flammable refrigerants, but the sensitivity 
may not be adequate, or may need re-calibration. 
(Detection equipment shall be calibrated in a 
refrigerant-free area.) Ensure that the detector is not 
a potential source of ignition and is suitable for the 
refrigerant used. Leak detection equipment shall be 
set at a percentage of the LFL of the refrigerant and 
shall be calibrated to the refrigerant employed and 
the appropriate percentage of gas (25 % maximum) 
is confirmed. Leak detection fluids are suitable for 
use with most refrigerants but the use of detergents 
containing chlorine shall be avoided as the chlorine 
may react with the refrigerant and corrode the copper 
pipe-work.
• If a leak is suspected, all naked flames shall be 
removed or extinguished.
• If a leakage of refrigerant is found which requires 
brazing, all of the refrigerant shall be recovered 
from the system, or isolated (by means of shut off 
valves) in a part of the system remote from the leak. 
Oxygen free nitrogen (OFN) shall then be purged 
through the system both before and during the 
brazing process.
2.15  Removal and evacuation
• When breaking into the refrigerant circuit to make 
repairs or for any other purpose, conventional 
procedures shall be used. However, it is important 
that best practice is followed since flammability is a 
consideration.
• The following procedure shall be adhered to:
• remove refrigerant;
• purge the circuit with inert gas;
• evacuate;
• purge again with inert gas;
• open the circuit by cutting or brazing.