2
42XPP
The following field-supplied items are required to complete the installation.
Wall sleeve,Wall cap, Finishing tape (PVC film), Fastening tape, Pipe insulation, Drain hose (I.D. 16-17 mm), Sealer
putty.
Name Specification
Connection pipe
050 Ø(1/2”)12,70mm(Gas)/Ø(1/4”)6,35mm(Liquid)
070, 100 Ø(5/8”)15,87mm(Gas)/Ø(3/8”)9,52mm(Liquid)
- Power supply cable
H07 RN-F (60245IEC66), cable with synthetic rubber
insulation and polychloroprene sheath
- Electrical connecting cable between indoor and
outdoor unit
Accessories
Description Part number
42XPP
050, 070 100
Photocatalytic filter + Electrostatic filter 42PHW9103 •
Photocatalytic filter + Electrostatic filter + Carbon filter 42PHW9104 •
Installing the wall hanging bracket
Installation
• (See fig. 5). The piping can be connected in the four
ways indicated by e, f, g and h. When the piping
is connected to points e, f or h, remove the knock-
out either at the side or at the bottom of the unit.
• Installthewallhangingbracketsothatitislevel.Usea
plumb line i if necessary (See fig. 6).
• Besuretoleavetheclearancespaces.
• Ifthewallhangingbracketisnotlevel,watermaydrip
onto the floor.
• Installthewallhangingbracketwithafixingthatis
strong enough to withstand the weight of the unit.
• Beforeinstallingthewallhangingbracket,removeit
from the unit by pushing at the indicated parts at the
bottom of the body (Remove screw j).
• Fastenthewallhangingbrackettothewallwith4or
more screw anchors through the holes near the outer
edge of the bracket.
• Installthewallhangingbracketsothatthereisnogap
between the bracket and the wall.
• Checkthatthewallhangingbracketdoesnotmove.
This can cause noise during operation.
• Iftheunitisremovedfromthewallhangingbracket
after installing it onto the wall, remove it by pushing up
the indicated MARKS (
) at the bottom of the body.
IMPORTANT NOTE:
This unit has no refrigerant expansion device.
Installation Material
The following installation accessories are supplied with unit. Use them as required.
Name and shape Q.ty Use
Wall hanging bracket 1 For indoor unit installation
Screws4xL10 2 For fixing unit and hanging bracket
Screwsanchorsandscrews4xL25
Washers Ø 12
5+5+5 For wall hanging bracket installation (050, 070)
Screws3xL14 1 For cordless remote control mounting bracket installation
Screws5xL25 14 For wall hanging bracket installation (100)
Cordless remote control mounting bracket 1 For cordless remote control installation
English