13
Staged Air Volume
All 48FC-08-16 units with EcoBlue™ technology come factory 
set to automatically adjust the indoor fan motor speed in sequence 
with the unit’s ventilation, cooling, and heating operation. See Ta-
ble 1 for fan operation for various modes.
COOLING
Condenser Coil
The condenser coil is fabricated with round tube copper hairpins 
and plate fins of various materials and/or coatings (see Model 
Number Nomenclature in Appendix A to identify the materials 
provided in this unit). The coil may be one-row or composite-type 
two-row. Composite two-row coils are two single-row coils fabri-
cated with a single return bend end tubesheet.
Condenser Coil Maintenance and Cleaning 
Recommendation
Routine cleaning of coil surfaces is essential to maintain proper 
operation of the unit. Elimination of contamination and removal of 
harmful residues will greatly increase the life of the coil and ex-
tend the life of the unit. The following maintenance and cleaning 
procedures are recommended as part of the routine maintenance 
activities to extend the life of the coil.
REMOVE SURFACE LOADED FIBERS
Surface loaded fibers or dirt should be removed with a vacuum 
cleaner. If a vacuum cleaner is not available, a soft non-metallic 
bristle brush may be used. In either case, the tool should be ap-
plied in the direction of the fins. Coil surfaces can be easily dam-
aged (fin edges can be easily bent over and damage to the coating 
of a protected coil) if the tool is applied across the fins.
NOTE: Use of a water stream, such as a garden hose, against a 
surface loaded coil will drive the fibers and dirt into the coil. This 
will make cleaning efforts more difficult. Surface loaded fibers 
must be completely removed prior to using low velocity clean wa-
ter rinse.
PERIODIC CLEAN WATER RINSE
A periodic clean water rinse is very beneficial for coils that are ap-
plied in coastal or industrial environments. However, it is very im-
portant that the water rinse is made with a very low velocity water 
stream to avoid damaging the fin edges. Monthly cleaning as de-
scribed below is recommended. Rinsing coils in the opposite di-
rection of airflow is recommended.
ROUTINE CLEANING OF COIL SURFACES
Periodic cleaning with Totaline
®
 environmentally balanced coil 
cleaner is essential to extend the life of coils. This cleaner is avail-
able from Replacement Components Division as P/N: P902-0301 
for a one gallon container, and P/N: P902-0305 for a 5 gallon con-
tainer. It is recommended that all coils, including standard alumi-
num, pre-coated, copper/copper or e-coated coils be cleaned with 
the Totaline environmentally balanced coil cleaner as described 
below. Coil cleaning should be part of the unit’s regularly sched-
uled maintenance procedures to ensure long life of the coil. Failure 
to clean the coils may result in reduced durability in the environ-
ment.
Avoid use of:
• coil brighteners
• acid cleaning prior to painting
• high pressure washers
• poor quality water for cleaning
Totaline environmentally balanced coil cleaner is nonflammable, 
hypo-allergenic, non-bacterial, and a USDA accepted biodegrad-
able agent that will not harm the coil or surrounding components 
such as electrical wiring, painted metal surfaces, or insulation. Use 
of non-recommended coil cleaners is strongly discouraged since 
coil and unit durability could be affected.
Clean coil as follows:
1. Turn off unit power, tag disconnect.
2. Remove all screws from the top panel except the screws 
securing the condenser fan to the top panel. See Fig. 19.
Fig. 19 — Location of Screws and Coil Corner Post
3. Remove condenser coil corner post. See Fig. 19. To hold 
top panel open, place coil corner post between top panel 
and center post. See Fig. 20.
Table 1 — Percentage of Vdc Setting
UNIT HIGH COL HEAT LOW COOL VENT
48FC08 100% 100% 60% 60%
48FC09 100% 100% 50% 50%
48FC12 100% 100% 60% 60%
48FC14 100% 100% 60% 60%
48FC16 100% 100% 66% 66%
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, 
death and/or equipment damage.
This system uses Puron
®
 refrigerant which has higher 
pressures than R-22 and other refrigerants. No other 
refrigerant may be used in this system. Gauge set, hoses, and 
recovery system must be designed to handle Puron refrigerant. 
If unsure about equipment, consult the equipment 
manufacturer.
Top Panel
Remove screws 
from all sides
of top panel
Remove
Screws
Condenser
Fan
Condenser
Coil
Condenser Coil
Corner Post
Center
Post
Compressor
Access Panel