34
DIRTY CONTROLLER TEST PROCEDURE
1. Press the controller’s test/reset switch for two seconds.
2. Verify that the controller’s Trouble LED flashes.
Dirty Sensor Test
The dirty sensor test provides an indication of the sensor’s ability 
to compensate for gradual environmental changes. A sensor that 
can no longer compensate for environmental changes is consid-
ered 100% dirty and requires cleaning or replacing. A field pro-
vided SD-MAG test magnet must be used to initiate a sensor dirty 
test. The sensor’s Dirty LED indicates the results of the dirty test 
as shown in Table 3.
DIRTY SENSOR TEST PROCEDURE
1. Hold the test magnet where indicated on the side of the 
sensor housing for two seconds.
2. Verify that the sensor’s Dirty LED flashes.
Changing the Dirt Sensor Test
By default, sensor dirty test results are indicated by:
• The sensor’s Dirty LED flashing.
• The controller’s Trouble LED flashing.
• The controller’s supervision relay contacts toggle.
The operation of a sensor’s dirty test can be changed so that the 
controller’s supervision relay is not used to indicate test results. 
When two detectors are connected to a controller, sensor dirty test 
operation on both sensors must be configured to operate in the 
same manner.
TO CONFIGURE THE DIRTY SENSOR TEST OPERATION
1. Hold the test magnet where indicated on the side of the 
sensor housing until the sensor’s Alarm LED turns on and 
its Dirty LED flashes twice (approximately 60 seconds).
2. Reset the sensor by removing the test magnet then holding 
it against the sensor housing again until the sensor’s Alarm 
LED turns off (approximately 2 seconds).
Remote Station Test
The remote station alarm test checks a test/reset station’s ability to 
initiate and indicate an alarm state.
SD-TRK4 Remote Alarm Test Procedure
1. Turn the key switch to the RESET/TEST position for 
seven seconds.
2. Verify that the test/reset station’s Alarm LED turns on.
3. Reset the sensor by turning the key switch to the 
RESET/TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns off.
Remote Test/Reset Station Dirty Sensor Test
The test/reset station dirty sensor test checks the test/reset station’s 
ability to initiate a sensor dirty test and indicate the results. It must 
be wired to the controller as shown in Fig. 48 and configured to 
operate the controller’s supervision relay. For more information, 
see “Dirty Sensor Test” on page 34.
Fig. 48 — Remote Test/Reset Station Connections
IMPORTANT: Failure to follow this ALERT can result in 
an unnecessary evacuation of the facility.
Pressing the controller’s test/reset switch for longer than seven 
seconds will put the duct detector into the alarm state and 
activate all automatic alarm responses.
IMPORTANT: Failure to follow this ALERT can result in 
an unnecessary evacuation of the facility.
Holding the test magnet against the sensor housing for more 
than seven seconds will put the duct detector into the alarm 
state and activate all automatic alarm responses.
Table 3 — Dirty LED Test
FLASHES DESCRIPTION
1  0-25% dirty. (Typical of a newly installed detector)
2  25-50% dirty
3  51-75% dirty
4  76-99% dirty
IMPORTANT: Failure to follow this ALERT can result in 
an unnecessary evacuation of the facility.
Changing the dirty sensor test operation will put the detector 
into the alarm state and activate all automatic alarm responses. 
Before changing dirty sensor test operation, disconnect all 
auxiliary equipment from the controller and notify the proper 
authorities if connected to a fire alarm system.
IMPORTANT: Failure to follow this ALERT can result in 
an unnecessary evacuation of the facility.
This test places the duct detector into the alarm state. Unless 
part of the test, disconnect all auxiliary equipment from the 
controller before performing the test. If the duct detector is 
connected to a fire alarm system, notify the proper authorities 
before performing the test.
IMPORTANT: Failure to follow this ALERT can result in 
an unnecessary evacuation of the facility.
If the test/reset station’s key switch is left in the RESET/TEST 
position for longer than seven seconds, the detector will 
automatically go into the alarm state and activate all automatic 
alarm responses.
1
12
14
13
19
15
2
20
3
Reset/Test
Trouble
Power
Alarm
5
4
1
3
2
SD-TRM4 
2
1
TB3
18 VDC (-)
18 VDC (-)
+
−
Supervision
Relay
Contacts [3]
Wire must be
added by
installer
Smoke Detector
Controller
Auxiliary 
Equipment