SETPOINTS
(cont)
VENTMAX H 4.4 V 2 to 10 vdc
DCV MAXIMUM DAMPER POSITION AT HIGH SPEED. Only displays
if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2
speed with 1 heat and 1 cool then set for COOLING ventilation. If using
3 speed with 1 heat and 2 cool then set for HIGH SPEED COOLING
ventilation.
VENTMIN L 3.7 V 2 to 10 vdc
DCV MINIMUM DAMPER POSITION AT LOW SPEED. Only displays if
unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2
speed with 1 heat and 1 cool then set for HEATING ventilation. If using 3
speed with 1 heat and 2 cool then set for LOW SPEED COOLING.
VENTMIN M 3.4 V 2 to 10 vdc
DCV MINIMUM DAMPER POSITION AT MEDIUM SPEED. Only
displays if unit is set for 3 speed with 1 heat and 2 cool. Set for
HEATING ventilation.
VENTMIN H 2.8 V 2 to 10 vdc
DCV MINIMUM DAMPER POSITION AT HIGH SPEED. Only displays
if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2
speed with 1 heat and 1 cool then set for COOLING ventilation. If using
3 speed with 1 heat and 2 cool then set for HIGH SPEED COOLING
ventilation.
ERV OAT SP
g
32°F
0°F to 50°F
(–18°C to 10°C);
increment by 1°F
ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR
TEMPERATURE SETPOINT
Only displayed when AUX1 O = ERV
EXH1 SET 50% 0 to 100%
Exhaust fan set point for single speed units. Based on OA Damper
position to activate power exhaust.
EXH1 L SET 65% 0 to 100%
EXHAUST FAN 1 SETPOINT AT LOW SPEED on 2 speed or 3 speed
with 1 heat and 2 cool. Based on economizer OA damper position to
activate power exhaust.
EXH1 M SET 60% 0 to 100%
EXHAUST POINT 1 SETPOINT AT MEDIUM SPEED. Only displays if
unit is set for 3 speed with 1 heat and 2 cool. Based on economizer OA
damper position to activate power exhaust.
EXH1 H SET 50% 0 to 100%
EXHAUST FAN 1 SETPOINT AT HIGH SPEED on 2 speed or 3 speed
with 1 heat and 2 cool. Based on economizer OA damper position to
activate power exhaust.
EXH2 L SET 80% 0 to 100%
EXHAUST FAN 2 SETPOINT AT LOW SPEED on 2 speed or 3 speed
with 1 heat and 2 cool. Based on economizer OA damper position to
activate power exhaust.
EXH2 M SET 77% 0 to 100%
EXHAUST FAN 2 SETPOINT AT MEDIUM SPEED. Only displays if
unit is set for 3 speed with 1 heat and 2 cool. Based on economizer OA
damper position to activate power exhaust.
EXH2 H SET 75% 0 to 100%
EXHAUST FAN 2 SETPOINT AT HIGH SPEED on 2 speed or 3 speed
with 1 heat and 2 cool. Based on economizer OA damper position to
activate power exhaust.
SYSTEM
SETUP
INSTALL 01/01/17 N/A
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG F F or C Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT CONV
Conventional or
HP
CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump input
from thermostat or controller
h
.
AUX2 IN W
SD/W or
HP(O)/HP(B)
In CONV mode:
SD + Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV mode
for W. Shutdown is not available in 2-speed fan mode
h
.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
FAN SPEED 2 speed
1 speed
2 speed
2SP H/C
3 speed
Sets the economizer controller operation based on 1 speed, 2 speed,
2 speed heat/cool (2SP H/C), or 3 speed supply fan.
NOTE: Multi-speed fan options also need Heat (W1) programmed in
AUX 2 In
h
.
FAN CFM 5000cfm
100 to 15000
cfm;
increment by 100
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate label for the specific unit.
AUX1 OUT NONE
NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
g
• EXH2 = second damper position relay closure for second exhaust fan
• SYS = use output as an alarm signal
OCC INPUT
INPUT or
ALWAYS
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac), the
24 vac is input “INPUT” to the OCC terminal. If no occupancy output
from the thermostat then change program to “ALWAYS” OR add a
jumper from terminal R to OCC terminal.
FACTORY DEFAULT NO NO or YES
Resets all set points to factory defaults when set to YES. LCD
will
briefly flash YES and change to NO but all parameters will change to
the factory default values.
NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed
values.
Table 19 — W7220 Menu Structure
a
(cont)
MENU PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
b
NOTES