104
OAU  Outside Air Unit Status  OAUDISP
OA.RN OAU System Run State
1=AUTO
2=OFF
3=TEST
OAU_RUN
OA.OP  OAU Operating Mode
0=Off
1=ERV (DCV)
2=Free Cooling
3=OA Tempering
4=Defrost
5=Test
6=Ext. Mode 1
7=Ext. Mode 2
8=Ext. Mode 3
OAU_MODE
UPC  UPC Software Version  xxxx  UPC_VER
OAU  OA Unit Software Version  xxxx  OAU_VER
2P.DM  OAU 2-position Damper  Close/Open  OAUDMPR
WHL  OAU Wheel Speed  xxx  %  OAUWHEEL
LAT  OAU Leaving Air Temp  xxx.x  °F  OAU_LAT
EXAT  OAU Exhaust Air Temp  xxx.x  °F  OAU_EXAT
OA.MN  Minimum Outside Air CFM  xxxxx  CFM  MINOACFM
DCV.M  Min DCV Outside Air CFM  xxxxx  CFM  MINDCVSP
OA.FS  OAU OA Fan Speed  xxx  %  OAFANSPD
A.OA  Actual Outside Air CFM  xxxxx  CFM  ACTOACFM
C.OA  Command Outside Air CFM  xxxxx  CFM  CMDOACFM
PE.OF  Power Exhaust CFM Offset xxxxx  CFM  EXOFFSET
EX.FS  OAU Exhaust Fan Speed  xxx  %  OAUPESPD
A.EX  Actual Exhaust Air CFM xxxxx  CFM  ACTEXCFM
C.EX  Command Exhaust Air CFM  xxxxx CFM  CMDEXCFM
BP.SP  Building Pressure Setpnt  x.xx  in H2O  OAU_BPSP
BP  Building Pressure  x.xx  in H2O  OAU_BP
TM.LO  OA Tempring Lockout Temp  xx  °F  OATMPLOC
TM.SP  OA Tempring SAT Setpoint  xx  °F  OATMPSPT
OA.HT  OAU Tempering Heater  xxx  %  OAHEATER
HRS  Component Run Hours  STRTHOUR
A1  Compressor A1 Run Hours  xxxxx.xx  hours  HR_A1 forcible
B1  Compressor B1 Run Hours  xxxxx.xx  hours  HR_B1  forcible
IDF1  Indoor Fan 1 Run Hours  xxxxx.xx  hours  HR_IDF1  forcible
IDF2  Indoor Fan 2 Run Hours  xxxxx.xx  hours  HR_IDF2  forcible
IDF3  Indoor Fan 3 Run Hours  xxxxx.xx  hours  HR_IDF3  forcible
HT.1  Heat Stage 1 Run Hours  xxxxx.xx  hours  HR_HTR_1  forcible
HT.2  Heat Stage 2 Run Hours  xxxxx.xx  hours  HR_HTR_2  forcible
PE.1  Power Exhaust1 Run Hours  xxxxx.xx hours  HR_PE_1  forcible
PE.2  Power Exhaust2 Run Hours  xxxxx.xx hours  HR_PE_2  forcible
ALRM  Alarm Relay Run Hours  xxxxx.xx hours  HR_ALM  forcible
CRC  Reheat1 Valve Run Hours  xxxxx.xx hours  HR_CRC  forcible
RH2.A  Reheat2 Valve A Run Hrs  xxxxx.xx hours  HR_RH2_A  forcible
RH2.B  Reheat2 Valve B Run Hrs  xxxxx.xx hours  HR_RH2_B  forcible
STRT  Component Starts
A1  Compressor A1 Starts xxxxxx  ST_A1  forcible
B1 
Compressor B1 Starts xxxxxx  ST_B1  forcible
IDF1  Indoor Fan 1 Starts  xxxxxx ST_IDF1 forcible
IDF2  Indoor Fan 2 Starts  xxxxx.xx ST_IDF2 forcible
IDF3  Indoor Fan 3 Starts  xxxxx.xx ST_IDF3 forcible
HT.1  Heat Stage 1 Starts  xxxxxx  ST_HTR_1  forcible
HT.2  Heat Stage 2 Starts  xxxxxx  ST_HTR_2  forcible
PE.1  Power Exhaust 1 Starts  xxxxxx  ST_PE_1  forcible
PE.2  Power Exhaust 2 Starts  xxxxxx  ST_PE_2  forcible
ALRM  Alarm Relay Starts  xxxxxx  ST_ALM forcible
CRC  Reheat1 Valve Starts  xxxxxx ST_CRC forcible
RH2.A  Reheat2 Valve A Starts  xxxxxx ST_RH2_A forcible
RH2.B  Reheat2 Valve B Starts  xxxxxx ST_RH2_B forcible
 APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table A — Mode — Run Status (cont)
ITEM EXPANSION RANGE UNITS 
CCN TABLE/
SUB-TABLE 
CCN POINT 
CCN 
WRITE 
STATUS