112
O.20M OAQ Sensor Value at 20mA 0 to 5000 2000 OAQ_20MA 25
H.4M RH Sensor Value at 4mA 0 to 50 % 0 RH_4MA 26
H.20M RH Sensor Value at 20mA 60 to 100 % 100 RH_20MA 26
OAU OUTSIDE AIR UNIT CONFIG. OAU_CFG
OA.TY Outdoor Air Unit Type
0=No OAU
1=ERV Module
0: no FIOP
1: FIOP EnergyX
OAU_TYPE 36
OA.FC Outside Air Fan Curve 0 to 999
1: 04
2: 05-06
3: 07
4: 08-12
5: 14
6: 17-20
7: 24-28
OAFANCRV
PE.FC Exhaust Air Fan Curve 0 to 999
1: 04, 1ph, and
econ
2: 04, 3ph, and
econ
3: 04, 1ph, and
no econ
4: 04, 3ph, and
no econ
5: 05-06 1ph
6: 05-06 3ph
7: 07
8: 08-12
9: 14
10: 17-20 and
econ
11: 17-20 and no
econ
12: 24-28
PEFANCRV
U.RUN OAU Unoccupied Operation No/Yes NO UNOCCRUN
OAU.F Shut Down on Fan Failure No/Yes Yes FATALOAU
M.WHL Modulating Wheel Install No/Yes NO MODWHEEL
OA.MN Minimum Outside Air CFM 0 to 32000 CFM
375: 04
800: 05-06
1000: 07
2500: 08-12
3000: 14
4000: 17-20
5000: 24-28
MINOACFM
DCV.M Min DCV Outside Air CFM 0 to 32000 CFM
100: 04
250: 05-06
600: 07
1000: 08-12
1500: 14-24
2000: 24-28
MINDCVSP
PEX.C Power Exhaust Control
0=Offset CFM
1=BP
0 PEX_CTL
PE.OF Power Exhaust CFM Offset -17000 to 17000 CFM - 200 EXOFFSET
BP.SP Building Pressure Setpnt - 0.25 to 0.25 in H2O 0.05 OAU_BPSP
OA.TM Outside Air Tempering Disable/Enable Disable OATEMPER
TM.LO OA Tempring Lockout Temp 0 to 80 °F 60 OATMPLOC
TM.SP OA Tempring SAT Setpoint 35 to 80 °F 55 OATMPSPT
OAC.K Outside Air CFM k Factor 0.8 to 1.2 1.0 OACFM_K
EXC.K Exhaust Air CFM k Factor 0.8 to 1.2 1.0 EXCFM_K
OAFB OAU Fan Boost Enable No/Yes No EFB_ENBL 17
ALM.O ALARM RELAY CONFIG. ALM_CFG 33
A.SPC SPT/SPRH Sensor Failure No/Yes Yes SPACE_AL
A.SRT SAT/RAT Sensor Failure No/Yes Yes SATRATAL
A.OAT OAT Thermistor Failure No/Yes Yes OAT_AL
A.CS Current Sensor Failure No/Yes No CS_AL
A.CMP Compressor Failure No/Yes Yes COMP_AL
A.CKT Refrig Circuit Failure No/Yes Yes CKT_AL
A.SSP
SSP Transducer Failure No/Yes Yes SSP_AL
A.SCT SCT Thermistor Failure No/Yes Yes SCT_AL
A.FAN Indoor Fan Failure No/Yes Yes FAN_AL
A.FIL Dirty Filter No/Yes Yes FILT_AL
A.TST Thermostat Failure No/Yes Yes TSTAT_AL
A.ECO Economizer Failure No/Yes Yes ECON_AL
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table H — Mode — Configuration (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT
PAGE
NO.