APPENDIX C — VARIABLE FREQUENCY DRIVE (VFD) (cont)
CONTROL SET POINT AND CONFIGURATION LOG
MODEL NO.: _____________________________________
SERIAL NO.: _____________________________________
DATE: ___________________________________________
TECHNICIAN: ____________________________________
SOFTWARE VERSIONS
MBB: CESR131504-_ _
ECB: CESR131249-_ _
MARQ: CESR131171-_ _
INDICATE UNIT SETTINGS BELOW
CONTROL TYPE: Thermostat/T55 Space Temp./T-56 Space Temp./T-58 Space Temp.
SET POINT Cooling Occupied: __________________ Unoccupied: __________________
Heating Occupied: __________________ Unoccupied: __________________
Table X — Mode — Configuration
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
Sub- TABLE
CCN POINT ENTRY
CONFIGURATION
SERVICE
CONFIGURATION
DISP DISPLAY CONFIGURATION DISPLAY
METR Metric Display No/Yes No DISPUNIT
LANG Language Selection
0=English
1=Spanish
2=French
3=Portuguese
0 LANGUAGE
PROT Password Enable Disable/Enable Enable PASS_EBL
PSWD Service Password 0000 to 9999 1111 PASSWORD
TEST Test Display LEDs Off/On Off
(display only, not
in table)
DISPTEST
UNIT UNIT CONFIGURATION UNIT
S.DLY Startup Delay 10 to 600 sec 30 STARTDLY
U.CTL Unit Control Type
2=Thermostat
3=Space Sensor
2 CTL_TYPE
T.CTL Thermostat Control Type
0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0 STATTYPE
FN.SW Fan Status Switch
0=No Switch
1=Normal Open
2=Normal Closed
0 FANSTCFG
FL.SW Filter Status Switch
0=No Switch
1=Normal Open
2=Normal Closed
0 FILSTCFG
FS.SW Fire Shutdown Switch
0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
SHTDNCFG
RM.SW Remote Occupancy Switch
0=No Switch
1=Normal Open
2=Normal Closed
0 REMOCCFG
SAT.T SAT Settling Time 10 to 900 sec 240 SAT_SET
RAT.S RAT Sensor Installed No/Yes No RAT_SENS
RH.S RH Sensor on OAQ Input No/Yes No RH_OAQ
RH.SW Space Humidity Switch
0=No Switch
1=Normal Open
2=Normal Closed
0 HUMSTCFG
TCS.C Temp Cmp Strt Cool Factr 0 to 60 mins 0 TCSTCOOL
TCS.H Temp Cmp Strt Heat Factr 0 to 60 mins 0 TCSTHEAT
I.FAN INDOOR FAN CONFIG AFAN_CFG
FTYP Indoor Fan Type
0=1- SPEED
1=LEN VFD
0
1: SAV option
FAN_TYPE
NSPD Number of Speeds 2, 3, or 7 2 NUM_SPDS
OC.FN Fan On When Occupied No/Yes Yes OCC_FAN
IDF.F Shut Down on IDF Failure No/Yes Yes FATALFAN
FS.MX Supply Fan Maximum Speed 80 to 100 100 SPEEDMAX
FS.VN Fan Speed - Ventilation 0 to 100 % 67 FSPDVENT
FS.AQ Fan Speed - IAQ Override 0 to 100 % 100 FSPDAQOR
FS.E1
Fan Speed - Free Cool Lo 0 to 100 % 67 FSPDECO1
FS.CL Fan Speed - Mech Cooling 60 to 100 % 67 FSPDCOOL
FS.RH Fan Speed - Reheat2 65 to 100 % 100 FSPDREHT