30
Using the Keypad with Settings and Parameters —
To use the keypad when working with Setpoints, System
and Advanced Settings, Checkout tests and Alarms:
3. Navigate to the desired menu.
4. Press the
(Enter) button to display the first item in
the currently displayed menu.
5. Use the
and buttons to scroll to the desired
parameter.
6. Press the
(Enter) button to display the value of the
currently displayed item.
7. Press the
button to increase (change) the displayed
parameter value.
8. Press the
button to decrease (change) the displayed
parameter value.
NOTE: When values are displayed, pressing and
holding the
or button causes the
display to automatically increment.
9. Press the
(Enter) button to accept the displayed
value and store it in nonvolatile RAM.
10. “CHANGE STORED” displays.
11. Press the
(Enter) button to return to the current
menu parameter.
12. Press the (MenuUp/Exit)buttontoreturntothe
previous menu.
Menu Structure
IMPORTANT: Table 6 illustrates the complete hierarchy.
Your menu parameters may be different depending on your
configuration. For example if you do not have a DCV (CO
2
)
sensor, then none of the DCV parameters appear.
The menu hierarchy has been modified to reflect controller
configuration for 2--speed indoor fan application in the
Staged Air Volume option.
NOTE: Some parameters in the menus use the letters MA
or MAT, indicating a mixed air temperature sensor
location before the cooling coil. This unit application has
the control sensor located after the cooling coil, in the fan
section, where it is designated as (Cooling) Supply Air
Temperature or SAT sensor.
Table 6 – Menu Structure
a1
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
b
EXPANDED PARAMETER NAME
Notes
STA TUS ECON AVAIL NO YES/NO ECONOMIZING AVAIALBLE
YES = economizing available; the system can use outside air for free
coo ling w hen required
ECONOMIZING NO YES/NO ECONOMIZING ACTIVE
YES = Outside air being used for 1
st
stag e cooling.
NO = Ec o no m izing not active
OCCUPIED NO YES/NO OCCUPIED
YES = OCC signal recei ved from sp ace thermostat
or unitary controlle r.
YES = 24 V ac on termi nal OCC.
NO = 0 Vac on termi nal OCC.
HEAT PUMP n/a
c
COOL
HEAT
HEAT PUMP MODE
(Not available on 2---Speed configurati on)
COOL Y1 ---IN OFF ON/OFF FIRST STAGE COOLING DEMAND (Y1 ---IN)
Y1---I si g nal from sp ac e thermostat or uni t a ry cont rolle r for Cooling Stag e 1.
ON = 24 Vac on termi nal Y 1---I
OFF = 0Vac on terminal Y1---I
COOL Y1---OUT OFF ON/OFF FIRST STAGE COOLING RELA Y OUTPUT
ON = 24 Vac on terminal Y1---O; Stage 1 mechanical cooling called on
OFF = 0 V ac on termi nal Y1---O; no mechanic al cooling
COOL Y2 ---IN OFF ON/OFF SECOND STAVE COO LI NG DEMA ND (Y2---IN)
Y2---I si g nal from sp ac e thermostat or uni t a ry cont rolle r for Cooling Stag e 2.
ON = 24 Vac on termi nal Y 2---I
OFF = 0 V ac on terminal Y2---I
COOL Y2---OUT OFF ON/OFF SECOND STAGE COOLING RELA Y OUTPUT
ON = 24 Vac on terminal Y2---O; Stage 2 mechanical cooling called on
OFF = 0 V ac on terminal Y 2---O; no Stage 2 mechanical cooling
MA TEMP nn_F(or_C) 0 to 140_F
(---18 to 60_C)
SUPPLY AIR TEMPERA TR UE, Cooling Mode
Disp lays value of measured mixed /cooled air from SAT sensor in fan
section.
D ispl ays --- --- . --- if n ot co nn ect ed, sh ort or o ut --- o f --- r an ge. S ee M en u No te 2
DA TEMP nn_F(or_C) 0 to 140_F
(---18 to 60_C)
DISCHARGE AIR TEMPERATRUE, after Heating section
(Accessory sensor required)
Displays when Discharge Air sensor is connected and displays measured
di s c harg e temperat ure.
D ispl ays --- --- --- --- --- --- i f s en sor sen ds in val id v al ue, if n ot co nne ct ed, sh ort
or out---of---range.
OA TEMP nn_F(or_C) ---40 to 140_F
(---40 to 60_C)
OUTSIDE AIR TEMPERATRUE
Displays meas ure d value of outd o or ai r temp e rat ure.
D ispl ays --- --- --- --- --- --- i f s en sor sen ds in val id v al ue, if n ot co nne ct ed, sh ort
or out---of---range.
OA HUM nn% 0 to 100% OUTSIDE AIR RELATIVE HUMI DI TY
Displays measure d value of out d o o r humidity from OA enthalp y se ns o r.
48HC48LC