EasyManua.ls Logo

Carrier 58PB - Step 2 - Provide Air for Combustion and; Step 3 - Assemble Furnace; Draft Hood

Carrier 58PB
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HEATING
&
COOLING
58ED,PB
Horizontal
Gas-Fired
Furnaces
Table
3
Alcove
Clearances
(in.)
TOP
SIDES
BACK
DRAFT
HOOD
SINGLE
WALL
VENT
8
6
8*
18f
Line
Contact
6
•With
draft
hood
in
front
of
furnace
fWith
draft
hood
on
back
of
furnace
Step
2
Provide
Air
For
Combustion
and
Ventilation
For
an
unconfined
space
(more
than
50
cu
ft
of
volume
per
1,000
Btu
of
aggregate
input
rating
of
all
appliances
installed
in
that
space)
such
as
a
base¬
ment
or
attic,
infiltration
air
is
normally
adequate
to
provide
air
for
combustion,
ventilation
and
dilution
of
flue
gases.
Adjoining
rooms
may
be
included
if
there
are
no
doors
between
the
rooms
For
a
confined
space,
where
air
is
taken
from
an
interior
space,
2
permanent
openings
of
equal
area
are
required.
One
opening
must
be
within
12
in.
of
the
ceiling
and
the
other
must
be
within
12
in.
of
the
floor.
Each
opening
must
have
a
free
area
of
at
least
1
sq
in.
per
1000
Btu
of
total
input
rating
but
not
less
than
100
sq
inches.
If
the
outside
air
is
supplied
to
a
confined
space,
then
the
2
openings
must
be
equal
and
located
as
above
and
the
free
area
of
each
must
be:
A
CAUTION
Whenever
this
furnace
is
installed
in
an
area
along
with
one
or
more
gas
appliances,
the
total
Btu
input
of
all
appliances
must
be
included
when
determining
the
free
area
requirements
for
combustion
and
ventilation
air
openings.
When
ducts
are
used,
they
must
be
of
the
same
cross-
sectional
area
as
the
free
area
of
the
openings
to
which
they
connect.
The
minimum
dimension
of
rectangular
air
ducts
must
not
be
less
than
3
inches.
The
free
area
through
a
design
of
louver
or
grille
should
be
used
in
calculating
the
size
opening
required
to
provide
the
free
area
specified.
If
the
design
and
free
area
is
not
known,
it
may
be
assumed
that
wood
louvers
have
20-25%
free
area
and
metal
louvers
and
grilles
have
60-75%
free
area.
Screens
used
must
not
be
smaller
than
1
/4
in.
mesh
and
louvers
shall
be
fixed
in
the
open
posi¬
tion
or
interlocked
with
the
equipment
so
that
they
are
opened
automatically
during
equipment
operation.
A
WARNING
Do
not
block
the
combustion
air
openings
in
the
furnace.
Any
blockage
will
result
in
improper
com¬
bustion
and
may
result
in
a
fire
hazard
or
unsafe
condition
1.
Onesqin.
per
4,000
Btu
of
total
input
rating
when
the
air
is
directly
communicated
from
the
outdoors.
2.
One
sq
in.
per
4,000
Btu
of
total
input
rating
when
the
air
is
brought
in
through
vertical
ducts.
3
One
sq
in.
per
2,000
Btu
of
total
input
rating
when
the
air
is
transferred
through
horizontal
ducts.
LINE
CONTACT
ONLY
PERMISSIBLE
BETWEEN
TOP
CORNERS
OF
FURNACE
AND
BUILDING
JOISTS,
STUDS
OR
FRAMING.
KEEP
ALL
INSULATING
MATERIAL
CLEAR
OF
FURNACE.
INSULATING
MATERIALS
MAY
BE
COMBUSTIBLE.
METAL
EXTENDING
12
IN.
FROM
UNDER
COMBUSTION
CHAMBER
Fig.
2
Attic
Installation
Showing
Point
Contact
A
CAUTION
For
an
attic
installation,
keep
insulation
12
in.
or
more
away
from
any
furnace
openings.
Some
types
of
insulating
materials
may
be
combustible.
Step
3
Assemble
Furnace
The
burner
and
controls
are
shipped
in
place
and
the
furnace
high-
and
low-voltage
wiring
is
complete
to
facilitate
the
installa¬
tion.
Low-voltage
wiring
to
the
field-supplied
thermostat
is
necessary
to
complete
the
unit
wiring
(see
Step
7
Make
Electrical
Connections).
In
order
to
accommodate
all
the
possible
field
installa¬
tions
that
may
exist,
the
unit
is
designed
so
that
the
gas
valve,
controls
and
draft
hood
assembly
may
be
assembled
on
either
side
of
the
furnace.
Refer
to
Com¬
ponent
Reversal
section
for
details.
After
reversal
(if
required),
return
to
this
section.
A
CAUTION
Remove
cardboard
shipping
insert
from
eye
of
the
blower
scroll
before
energizing
blower.
DRAFT
HOOD
In
order
to
save
shipping
space
the
draft
hood
is
shipped
disassembled
(on
models
125
and
140
the
left
panel
is
spotwelded
in
place).
Remove
the
draft
hood
components
from
the
blower
compartment
(on
some
models
the
panels
might
be
packed
outside
the
furnace
jacket).
On
the
models
50,
75
and
100
there
will
Manufacturer
reserves
the
right
to
discontinue,
or
change
at
any
time,
specifications
or
designs
without
notice
and
without
incurring
obligations.
Book
I
I
1
4
PC101
Catalog
No
535-834
Printed
in
U
S
A
Form
58ED.PB-1
SI
Pg
3
6-85
Replaces:
58PB-1SI
Tab
l6a
18a
For
replacement
items
use
Carrier
Specified
Parts

Related product manuals