APPENDIX E — BACNET IP POINTS (cont)
LEGEND
OBJECT NAME OBJECT TYPE INSTANCE OPTION PV ACCESS DESCRIPTION
FACTORY_fMaxOvrA AV 325 RO Max Frequency Override A
FACTORY_fMaxOvrB AV 326 RO Max Frequency Override B
FACTORY_fMinOvr AV 328 RO Min Frequency Override
FACTORY_freq_60H BV 96 RO 60Hz Sel (No=50, Yes=60)
FACTORY_heat_sel BV 98 RO Evap Heater Installed
FACTORY_lastspda AV 329 RO Low Amb. Start Spd A
FACTORY_lastspdb AV 330 RO Low Amb. Start Spd B
FACTORY_leak_chk BV 102 RO Leakage Charge Detection
FACTORY_loambopt BV 101 RO Low Ambient Option (STD)
FACTORY_mfg_tier AV 322 RO Tier 0=STD, 1=MID, 2=HI
FACTORY_mst_slv BV 99 RO Master Slave Setup
FACTORY_probrine BV 97 RO Process Brine Evap
FACTORY_unitsize AV 320 RO Unit Capacity
FACTORY_voltage AV 321 RO Power Supply Voltage
FACTORY2_eco_cnfa AV 333 RO Economizer A Steps Numb
FACTORY2_eco_cnfb AV 334 RO Economizer B Steps Numb
FACTORY2_exvmax_a AV 331 RO EXV A Maximum Steps Numb
FACTORY2_exvmax_b AV 332 RO EXV B Maximum Steps Numb
FACTORY2_vfd_cmp AV 335 RO Nb VFD Compressor
FACTORY2_vfd_fana AV 336 RO Nb Fan Drive Cir A
FACTORY2_vfd_fanb AV 337 RO Nb Fan Drive Cir B
FAN_CFG_cp_factA AV 527 RO Compressor Factor A
FAN_CFG_cp_factB AV 528 RO Compressor Factor B
FAN_CFG_fan_ctrl BV 119 RO Fan Ctrl Type (Vari,Fix), Optimization Parameters
FAN_CFG_fan_hlim AV 522 RO Fan Max Frequency
FAN_CFG_fan_llim AV 523 RO Fan Min Frequency
FAN_CFG_fldp_kpa AV 516 RO Fan Low DP PI, Kp, Cir A
FAN_CFG_fldp_kpb AV 519 RO Fan Low DP PI, Kp, Cir B
FAN_CFG_fldp_nia AV 518 RO Fan Low DP PI, NI Cir A
FAN_CFG_fldp_nib AV 521 RO Fan Low DP PI, NI Cir B
FAN_CFG_fldp_tia AV 517 RO Fan Low DP PI, Ti Cir A
FAN_CFG_fldp_tib AV 520 RO Fan Low DP PI, Ti Cir B
FAN_CFG_fldtfact AV 529 RO Fan Low Dis. Factor
FAN_CFG_n_coilsA AV 525 RO Cir Cond Coil Number A
FAN_CFG_n_coilsB AV 526 RO Cir Cond Coil Number B
FAN_CFG_os_d_amp AV 532 RO Opt. Disturbance Ampl.
FAN_CFG_os_d_per AV 533 RO Opt. Disturbance Period
FAN_CFG_os_f_pow AV 534 RO Opt. Freeze Power Tol.
FAN_CFG_sct_bias AV 536 RO SCT bias at start
FAN_CFG_sct_decr AV 538 RO Decrement SCT bias time
FAN_CFG_sct_tim AV 537 RO Total SCT bias time
FAN_CFG_sync_Kp AV 524 RO Sychronizing Output Kp
FAN_CFG_xt_enabl BV 120 RO Optimization Enable
FAN_CFG_xt_in_tl AV 531 RO Opt. Deviation Tolerance
FAN_CFG_xt_s_smp AV 530 RO Stablility Sample Nb
FAN_CFG_xtos_flt AV 535 RO Opt. Filter Time
FAN_CTRL_fan_f_a AV 249 IR RO Fan Freq Cir A
FAN_CTRL_fan_f_b AV 257 IR RO Fan Freq Cir B
AV Analog Value IR Intrinsic Reporting
BV Binary Value RO Read Only
CMD Command RW Read Write
COV Change of Value TL Trend Log

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier AquaForce 30XV400 and is the answer not in the manual?

Carrier AquaForce 30XV400 Specifications

General IconGeneral
Model30XV400
Compressor TypeTwin-screw
RefrigerantR-134a
Number of Compressors2
Cooling Capacity400 tons
Power Supply460V/3Ph/60Hz
Sound PerformanceLow noise

Related product manuals