EasyManua.ls Logo

Carrier AquaForce B Series - Page 206

Carrier AquaForce B Series
358 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
206
VFD ALARM RESET
As long as communication is established between the Carrier
Controller controls and the VFD, most alarms can be reset di-
rectly through the chiller control system.
VFD REPLACEMENT PROCEDURE
If required, VFDs can be replaced and programmed with the
following procedures:
1. Disconnect power from unit. Wait a minimum of 20 minutes
before continuing (30XV140-325) or 40 minutes
(30XV350-500).
2. Disconnect electrical power and communication connections
from drive.
3. Unbolt and remove drive from inside the powerbox, taking
care to support drive at all times during the procedure.
Larger drives are equipped with lifting lugs which must be
used to support the load.
4. Lift, position, and fasten replacement drive to powerbox.
Tighten all bolts securely.
5. Connect power, control, VFD enable, and high pressure
switch wiring to drive. For wiring details for fan drives, see
Fig 88. Use the same knockout openings on new drive as on
drive being replaced. For compressor drives, the high-pres-
sure switch, VFD enable, and heater wiring also need to be
connected. See Fig. 89 for wiring details for compressor
drives. Torque connections are shown in Table 166.
Fig. 88 — Fan Drive Wiring
Fig. 89 — Compressor Drive Wiring
WARNING
After unit power is disconnected, wait at least 20 minutes
(30XV140-325) or 40 minutes (30XV350-500) for the
VFD capacitors to discharge before opening drive. Failure
to do so presents an electrical shock hazard and may result
in personal injury.
CAUTION
Use all proper rigging procedures and precautions when
moving VFDs to avoid damage to the equipment.
IMPORTANT: Ensure high pressure switch (HPS) and
VFD enable wiring are connected to compressor VFD.
Compressor will not run without HPS and VFD enable
wiring connection.
NOTE: For 30XV140-500 ton units, the VFD
heater shown is physically located on bottom
of enclosure but is wired as shown.
FOR PROPER OPERATION OF THE DRIVE
SAFETY STOP FEATURE
FOR PROPER OPERATION OF THE DRIVE
SAFETY STOP FEATURE
LEGEND
HW Shutdown Hard-wired Shutdown

Table of Contents

Related product manuals