APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Maintenance\LIMITS - Control Limits (cont)
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
ENV fan high dp stp B PSI (Kpa) fhdpstpb N N/A
ENV low dp act B PSI (Kpa) ldpactb N N/A
ENV low dp stp B PSI (Kpa) ldpstpb N N/A
ENV high sp act B PSI (Kpa) hspactb N N/A
ENV high sp stp B PSI (Kpa) hspstpb N N/A
ENV low sp act B PSI (Kpa) lspactb N N/A
ENV low sp stp B PSI (Kpa) lspstpb N N/A
ENV low sp delta B
kPa lspdcpb N N/A
dgt_act B °F (°C) dgtactb N N/A
dgt_stp B °F (°C) dgtstpb N N/A
Cmp Env Min SST A °F (°C) sstMinA N N/A
Cmp Env Max SST A °F (°C) sstMaxA N N/A
Cmp Env Min SDT A °F (°C) sdtMinA N N/A
Cmp Env Max SDT A °F (°C) sdtMaxA N N/A
Cmp Env Min SST B °F (°C) sstMinB N N/A
Cmp Env Max SST B °F (°C) sstMaxB N N/A
Cmp Env Min SDT B °F (°C) sdtMinB N N/A
Cmp Env Max SDT B °F (°C) sdtMaxB N N/A
Max Compressor Rate maxinc N N/A
Maintenance\M_MSTSLV - Master Slave Control
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
MASTER/SLAVE CONTROL
Unit is Master or Slave 0=Master
1=Slave
mstslv N N/A
Master Control Type
1=Local
2=Remote
3=CCN
ms_ctrl
NN/A
NN/A
NN/A
Master/Slave Ctrl Active FALSE/TRUE ms_activ N N/A
Lead Unit is the: Master/Slave lead_sel N N/A
Slave Chiller State slv_stat N N/A
Slave Chiller Total Cap 0 to 100 % slv_capt N N/A
Lag Start Delay min l_strt_d N N/A
Lead/lag Hours Delta hours ll_hr_d N N/A
Lead/lag Changeover No/Yes ll_chang N N/A
Lead Pulldown No/Yes ll_pull N N/A
Master/Slave Error ms_error N N/A