APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Service\FACTORY
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Unit Capacity unitsize N N/A
Power Supply Voltage voltage N N/A
60Hz Sel (No=50, Yes=60)
NO_YES - freq_60H N N/A
Tier 0=STD
1=MID
2-HI
mfg_tier N N/A
DX Evaporator Installed No/Yes dxcooler N N/A
Evap Pass Number 1 to 3 cpass_nb N N/A
Evap Heater Installed No/Yes heat_sel N N/A
Master Slave Setup No/Yes mst_slv N N/A
Energy Management Module No/Yes emm_nrcp N N/A
Low Ambient Option (STD) No/Yes loambopt N N/A
Leakage Charge Detection No/Yes leak_chk N N/A
Factory Password 113 fac_pass N N/A
Enable Max Frequency A No/Yes fMaxEnA N N/A
Enable Max Frequency B No/Yes fMaxEnB N N/A
Max Frequency Override A Hz fMaxOvrA N N/A
Max Frequency Override B Hz fMaxOvrB N N/A
Fan Freq Factor(0.7-1.1) Range: 0.7-1.1
Default: 1.0
fan_fact N N/A
Min Frequency Override Hz fMinOvr N N/A
Low Amb. Start Spd A
26 to 60 Hz lastspda N N/A
Low Amb. Start Spd B
26 to 60 Hz lastspdb N N/A
Service\FACTORY2
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
EXV A Maximum Steps Numb Range: 0 to 10000
Default: 0
exvmax_a N N/A
EXV B Maximum Steps Numb Range: 0 to 10000
Default: 0
exvmax_b N N/A
Economizer A Steps Numb Range: 0 to 15000
Default: 0
eco_cnfa N N/A
Economizer B Steps Numb Range: 0 to 15000
Default: 0
eco_cnfb N N/A
Nb VFD compressor Range: 0 to 2
Default: 0
vfd_cmp N N/A
Nb Fan Drive cir A Range: 0 to 3
Default: 0
vfd_fana N N/A
Nb Fan Drive cir B Range: 0 to 3
Default: 0
vfd_fanb N N/A