APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Service\MST_SLV
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
MASTER/SLAVE CONTROL
Master/Slave Select 0=disable
1=Master
2=Slave
ms_sel N N/A
Master Control Type 1=Local Control
2=Remote Control
3=CCN Control
ms_ctrl N N/A
Slave Address slv_addr N N/A
Lead Lag Select 0=Always Lead
1=Lag Once Failed Only
2=Lead/Lag Runtime Sel
lead_sel N N/A
Lead/Lag Balance Delta hours ll_bal_d N N/A
Lead/Lag Start Timer min lstr_tim N N/A
Lead Pulldown Time min lead_pul N N/A
Start If Error Higher °F (°C) start_dt N N/A
Lag Minimum Running Time min lag_mini N N/A
Lag Unit Pump Control 0=Stop if Unit Stops
1=Run if unit Stops
lag_pump N N/A
Chiller In Series No/Yes ll_serie N N/A
Service\SERVICE1
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Evaporator Fluid Type 1 = Water
2 = Med Brine
3=Low Brine
flui_typ N N/A
Entering Fluid Control No/Yes ewt_opt N N/A
Brine Freeze Setpoint Range: -20 to 34
Default: 34
°F (°C) freezesp N N/A
Brine Minimum Fluid Temp Range: -20 to 38
Default: 38
°F (°C) mini_lwt N N/A
Fast Capacity Recovery 0=Disabled
1=Quickstart Load
2=Fast Capacity Recovery
fastcapr N N/A
EWT Probe on Cir A Side No/Yes ewt_cirA N N/A
Service Password Range: 0 to 9999
Default: 88
ser_pass N N/A
Leakage Charge Threshold Range: 0 to 10
Default: 2.5
Volts leak_thr N N/A
Leakage Charge Timer Range: 0 to 600
Default: 60
min leak_tmr N N/A
Compressor RFI Filter En Off/On RFI_conf N N/A
Metric Units? (Blackbox) No/Yes metric N N/A
Send fan drive config? No/Yes fdrv_cfg N N/A