APPENDIX E — BACNET IP POINTS (cont)
LEGEND
OBJECT NAME OBJECT TYPE INSTANCE OPTION PV ACCESS DESCRIPTION
RESETCFG_dt_cr_fu AV 14 RO Delta T Full Reset Value
RESETCFG_dt_cr_no AV 13 RO Delta T No Reset Value
RESETCFG_oat_crfu AV 12 RO OAT Full Reset Value
RESETCFG_oat_crno AV 11 RO OAT No Reset Value
RESETCFG_spacr_fu AV 18 RO Space T Full Reset Value
RESETCFG_spacr_no AV 17 RO Space T No Reset Value
RESETCFG_v_cr_fu AV 16 RO Current Full Reset Value
RESETCFG_v_cr_no AV 15 RO Current No Reset Value
RUNTIME_HR_CP_A AV 73 IR RO Compressor A Hours
RUNTIME_HR_CP_B AV 75 IR RO Compressor B Hours
RUNTIME_hr_cpum1 AV 77 IR RO Evap Pump #1 Hours
RUNTIME_hr_cpum2 AV 78 IR RO Evap Pump #2 Hours
RUNTIME_HR_MACH AV 71 IR RO Machine Operating Hours
RUNTIME_hrfana01 AV 81 IR RO Circuit A Fan #1 Hours
RUNTIME_hrfana02 AV 82 IR RO Circuit A Fan #2 Hours
RUNTIME_hrfana03 AV 83 IR RO Circuit A Fan #3 Hours
RUNTIME_hrfana04 AV 84 IR RO Circuit A Fan #4 Hours
RUNTIME_hrfana05 AV 85 IR RO Circuit A Fan #5 Hours
RUNTIME_hrfana06 AV 86 IR RO Circuit A Fan #6 Hours
RUNTIME_hrfana07 AV 87 IR RO Circuit A Fan #7 Hours
RUNTIME_hrfana08 AV 88 IR RO Circuit A Fan #8 Hours
RUNTIME_hrfana09 AV 89 IR RO Circuit A Fan #9 Hours
RUNTIME_hrfana10 AV 90 IR RO Circuit A Fan #10 Hours
RUNTIME_hrfana11 AV 91 IR RO Circuit A Fan #11 Hours
RUNTIME_hrfana12 AV 92 IR RO Circuit A Fan #12 Hours
RUNTIME_hrfana13 AV 93 IR RO Circuit A Fan #13 Hours
RUNTIME_hrfana14 AV 94 IR RO Circuit A Fan #14 Hours
RUNTIME_hrfanb01 AV 95 IR RO Circuit B Fan #1 Hours
RUNTIME_hrfanb02 AV 96 IR RO Circuit B Fan #2 Hours
RUNTIME_hrfanb03 AV 97 IR RO Circuit B Fan #3 Hours
RUNTIME_hrfanb04 AV 98 IR RO Circuit B Fan #4 Hours
RUNTIME_hrfanb05 AV 99 IR RO Circuit B Fan #5 Hours
RUNTIME_hrfanb06 AV 100 IR RO Circuit B Fan #6 Hours
RUNTIME_hrfanb07 AV 101 IR RO Circuit B Fan #7 Hours
RUNTIME_hrfanb08 AV 102 IR RO Circuit B Fan #8 Hours
RUNTIME_hrfanb09 AV 103 IR RO Circuit B Fan #9 Hours
RUNTIME_hrfanb10 AV 104 IR RO Circuit B Fan #10 Hours
RUNTIME_hrfanb11 AV 105 IR RO Circuit B Fan #11 Hours
RUNTIME_hrfanb12 AV 106 IR RO Circuit B Fan #12 Hours
RUNTIME_hrfanb13 AV 107 IR RO Circuit B Fan #13 Hours
RUNTIME_hrfanb14 AV 108 IR RO Circuit B Fan #14 Hours
RUNTIME_st_cp_a AV 74 IR RO Compressor A Starts
RUNTIME_st_cp_b AV 76 IR RO Compressor B Starts
RUNTIME_st_mach AV 72 IR RO Machine Starts
RUNTIME_VIctA AV 79 IR RO VI Cycle Count A
RUNTIME_VIctB AV 80 IR RO VI Cycle Count B
SERVICE1_AntiFrz BV 113 RO Pump Rot. AntiFrz Protec
SERVICE1_apr_en AV 355 RO Approach Ctrl at Start??