11 - MAJOR SYSTEM COMPONENTS
11.1 - Compressors
61AF units use hermetic scroll compressors with vapour injection.
Each compressor is equipped with a crankcase oil heater, as
standard. Each compressor function is equipped with:
■ Anti-vibration mountings between the unit chassis and the
compressor(s).
■ A single pressure safety switch at the discharge.
11.2 - Lubricant
The compressors installed in these units have a specic oil charge,
indicated on the name plate of each compressor.
The oil level check must be done with the unit switched o, when
then suction and discharge pressures are equalised. The oil level
must be visible and above the middle of the sight-glass in the oil
equalisation line. If this is not the case, there may be an oil leak in
the circuit. Search and repair the leak, then recharge oil, so that it
reaches a level between the middle and three quarters of the sight-
glass (unit in vacuum).
ATTENTION: Too much oil in the circuit can cause a unit
defect. Use only oils which have been approved for the
compressors. Never use oils which have been exposed to air.
R-22 oils are absolutely not compatible with R-407C oils and
vice versa.
11.3 - Air evaporators
The 61AF coils are air evaporators with internally grooved copper
tubes with aluminium ns..
11.4 - Fans
Axial Flying Bird fans equipped with a rotating shroud and made of
composite recyclable material. The motors are three-phase, with
permanently lubricated bearings and insulation class F. See table
below.
According to the Regulation No. 327/2011 implementing Directive
2009/125/EC with regard to ecodesign requirements for fans driven
by motors with an electric input power between 125 W and 500 kW.
Product/ Option 61AF standard
61AF Standard
with option 11
Overall eciency % 36,6 38,0
Measurement category A A
Eciency category static static
Energy eciency
target N(2015)
N(2015) 40 N(2015) 40
Eciency level at
optimum eciency
point
43,3 37,4
Variable speed drive NO NO
Year of manufacture
See label on the
unit
See label on the
unit
Fan manufacturer Simonin Simonin
Motor manufacturer
A,O, Smith/Regal
Beloit
A,O, Smith/Regal
Beloit
Fan PN 00PSG000000100A 00PSG000000100A
Motor PN 00PPG000478400A 00PPG000480800A
Nominal power of the
motor
kW 0,88 2,09
Flow rate m
3
/s 3,59 4,07
Pressure at optimum
energy eciency
Pa 90 195
Nominal speed rpm 710 966
Specic ratio 1,002 1,002
Product/ Option 61AF standard
61AF Standard
with option 11
Relevant information to
facilitate the
disassembly,
recycling or removal of
the
product at the end of
life
See service manual See service manual
Relevant information to
minimise impact on the
environment
See service manual See service manual
11.5 - Electronic expansion valve (EXV) of the main
circuit
The EXV is equipped with a stepper motor that is con-trolled via
the EXV board.
11.6 - Electronic expansion valve (EXV) of the
economised circuit
The EXV is equipped with a stepper motor that is con-trolled via
the EXV board
11.7 - Four-way valve
The four-way valve allows the reversal of the refrigerant cycle,
required during the unit defrost phases.
11.8 - Moisture indicator
Located on the liquid line, permits control of the unit charge and
indicates moisture in the circuit. The presence of bubbles in the
sight-glass indicates an insucient charge or non-condensables
in the system. The presence of moisture changes the colour of
the indicator paper in the sight-glass.
11.9 - Filter drier
One-piece, brazed lter drier, located in the liquid line. The lter
drier keeps the circuit clean and moisture-free. The moisture
indicator shows when the lter drier to be changed. A dierence
in temperature between the lter inlet and outlet shows that the
element is dirty.
According to the Regulation No. 640/2009 and amendment 4/2014
implementing Directive 2009/125/EC with regard to ecodesign
requirements for electric motors.
Product/ Option
61AF
standard
61AF
Standard
with option
11
Motor type
Asynchrone
bi-vitesse
Asynchrone
bi-vitesse
Number of poles 8 6
Nominal input frequency Hz 50 50
Nominal voltage V 400 400
Number of phases 3 3
Motor included in the
application domain of the
regulation 640/2009 and
amendment 4/2014
Non Non
Sales leaet for exemption Article 2,1 Article 2,1
Ambient air temperature for
which the motor is
specically designed
°C 68,5 68,5