14.3 - Accessory 00PPG000488200- Heating System Manager type C
Heating system control (as accessory 00PPG000488100-) with
the possibility to obtain additional heating and domestic hot-
water production capacity from a district heating system
Allows control of a non-reversible heating system that includes a
61AF heat pump and two di󰀨erent heat emitter types and/or two 
independent comfort zones. For optimised energy e󰀩ciency the 
heat pump is controlled by a congurable weather compensation 
system.
The control box controls the heating and/or domestic hot-water
production support from a district heating system. The control box
supplies power to the circulating pumps. Hot-water production can
be permanent or programmable with a second setpoint at the heat
pump and control of a switching valve.
Heating system example: with the possibility to obtain additional heating and domestic hot-water
productioncapacity from a district heating system
GT1
GT4 P4 SV34
SV31
P2
P7
P1
GT5
P5
SV35
GT7
GT2
GT7:2
SV21
SV27
SV32
GT1:4
GT1:3
GT3
GT..
P..
SV..
61AF + HSM
Heating system
Floor heating
Domestic hot
water in
Hot water
Legend
Thermistors
GT1 Water temperature loop 1
GT1:3 Heat exchanger leaving water temperature, district heating
GT1:4 Heat exchanger entering water temperature, district heating
GT2 Domestic hot water tank temperature
GT3 Outdoor air temperature
GT4 Water temperature loop 2
GT5 Domestic hot water temperature
GT7 Additional domestic hot water tank temperature
GT7:2 Back-up heat exchanger temperature for domestic hot water
Pompes
P1 Pump for water loop 1 (radiators)
P2 External water pump for the heat pump
P4 Pump for water loop 2 (oor heating)
P5 Pump to pre-heat the domestic hot water valve loop
P7 Pump for domestic hot water circulation
Vannes
SV21 Valve for district heating heat exchanger for heating
SV27 Valve for district heating heat exchanger for domestic hot water
SV31 Three-way mixing valve for the back-up heater
SV32 Heating/domestic hot water change-over valve
SV34 Three-way control valve for water loop 2
SV35 Three-way mixing valve for domestic hot water
14 - HEATING SYSTEM MANAGER (HSM)