9.  Allow the unit to cool.
10. Set the generator’s main circuit breaker to its 
OFF (or OPEN) position.
11. Set the generator's AUTO/OFF/MANUAL switch 
to OFF. Remove the 7.5A and 15A fuses from the 
generator control panel. Disconnect the battery 
cables as outlined in “General Hazards” (page 
2).
12. Drain the oil and remove the oil filter. Replace 
the oil filter according to Section 3.4, “Changing 
the Oil Filter”. Replace the oil with synthetic oil 
as recommended in Section 3.3, “Changing the 
Engine Oil”.
13. Reconnect the battery cables as outlined in 
“General Hazards” (page 2) and insert the 7.5A 
and 15A fuses into the generator control panel. 
The generator is now ready for service.
3.2  USING THE AUTO/OFF/MANUAL 
SWITCH (FIGURE 3.1)
3.2.1 “AUTO” POSITION
Selecting this switch position activates fully auto-
matic system operation. It also permits starting and 
exercising the engine every seven days with the set-
ting of the exercise timer (see “Setting the Exercise 
Timer” section). This position also is used for remote 
starting, when it is set up.
3.2.2 “OFF” POSITION
This switch position shuts down the engine. This 
position also prevents automatic operation.
3.2.3 “MANUAL” POSITION
Set the switch to MANUAL to crank and start the 
engine. Transfer to standby power will not occur 
unless there is a utility failure.
Figure 3.1 – Generator Control Panel
12 VDC
ACCESSORY
OUTLET 7.5A MAX
EXERCISE
15A
SYSTEM FUSE
TIME
SET
AUTO
7.5A
OUTLET FUSE
OFF
MAN.
FLA S H IN G G R EEN LED =
4FLAS HIN G RED LEDS =
N O U T IL IT Y S EN S E
EX ER C IS ER N O T S ET
OVER CRANK
LOW OIL
OVER SPEED
HIGH TEMP.
SYSTEM SET
EXTERNAL
CIRCUIT
BREAKER
GFCI
 With the switch set to AUTO, the engine may 
crank and start at any time without warning. 
Such automatic starting normally occurs when 
utility power source voltage drops below a pre-
set level or during the normal exercise cycle. To 
prevent possible injury that might be caused by 
such sudden starts, always set the switch to OFF 
and remove both fuses before working on or 
around the generator or transfer switch. Then, 
place a “Do Not Operate” tag on the generator 
panel and on the transfer switch.
3.3  AUTOMATIC TRANSFER 
OPERATION
To select automatic operation, do the following:
1.  Make sure the transfer switch main contacts are 
set to their UTILITY position, i.e., loads con-
nected to the utility power source (Figure 3.2).
2.  Be sure that normal utility power source voltage 
is available to transfer switch terminal lugs N1 
and N2.
3.  Set the generator’s AUTO/OFF/MANUAL switch to 
AUTO.
4.  Set the generator’s main circuit breaker to its ON 
(or CLOSED) position.
With the preceding steps complete, the generator will 
start automatically when utility source voltage drops 
below a preset level. After the unit starts, loads are 
transferred to the standby power source. Refer to 
Section 3.4, “Sequence of Automatic Operation.”
3.3.1  12 VDC ACCESSORY OUTLET
The generator is equipped with a 12 VDC accessory 
outlet in the generator control panel (Figure 3.1). 
With the generator running or in standby mode, this 
outlet may be used to temporarily power low power 
accessories such as a work light, cell phone, radio or 
any other automotive style accessory. This outlet is 
capable of delivering a MAXIMUM of 7.5 amps. If the 
accessory to be used through this circuit demands 
too much power, the fuse that protects this circuit 
will melt open and the circuit will not be functional.
 This 12 VDC outlet draws power from the 
generator’s starting battery and extended use of 
this outlet may drain the battery and the engine 
may not start. This outlet should NOT be used 
for battery charging.
 13
Section 3 — Operation
15 kW Generator