Configuring the system
33CONNECTSTAT43 ©2022 Carrier.
Installation Guide All rights reserved.
16
Parameter Name/Description
Default and Range
REMOTE SENSOR Determines whether the remote sensor hardware input is:
NONE Not used
NONE or SPACE The outdoor temperature is acquired by Wi-Fi through the server,
based on the location of the mobile device used to connect the thermostat to a
router, or based on the ISP location, if a computer connects the thermostat to a
router.
OUTDOOR Senses the outdoor temperature
NOTE The outdoor temperature is not available if the thermostat is not connected to
Wi-Fi or if you do not select OUTDOOR.
AVERAGE Space temperature results from averaging the internal and the external
sensor
OCCUPANCY An external source is accessed to determine if the setpoints are
Occupied or Unoccupied. When Normally Open contacts close, the Occupied
setpoints are used.
NOTE When selected, NON-PROG is automatically set and is not displayed in the
Installer Settings until this parameter is changed.
FAULT INPUT An external source is used to detect a fault, as determined by the
attached Economizer.
SAT A sensor to provide a means of monitoring supply air temperature
NOTE SAT is a monitor-only point and has no effect on unit operation.
FILTER Used to detect a dirty filter. Contact closure causes FILTER REMINDER
message on home screen banner
NOTE This selection disables the timed air filter reminder functionality.
D:
R:
NONE
NONE
SPACE
OUTDOOR
AVERAGE
OCCUPANCY
FAULT INPUT
SAT
FILTER
SAT TEMP OFFSET Allows temperature offsets from -5° to 5°.
NOTE Only available when Remote Sensor Input > SAT is enabled.
D:
R:
0°F
-5 to 5°F
(1° increments)
MAX SETPOINT ERROR Allows a temperature deviation from setpoint of between 2 and
30°, to determine fault conditions (ID TEMP RANGE HIGH or LOW).
NOTE This value is added to the cooling setpoint or subtracted from the heating
setpoint.
D:
R:
10°F
2 to 30°F
(1° increments)
ID TEMP FLT INHIBIT Allows a time delay applied to the ID TEMP fault. The range is
adjustable from 10 to 240 minutes (60 default).
NOTE Allow for recovery time when transitioning from unoccupied to occupied periods.
D:
R:
60 mins
10 to 240 mins
(10 min increments)
COOL LOCKOUT Delays the cooling equipment demands if the outdoor air temperature
is below the selected value. There is a SYSTEM EVENT warning if the mode and space
temperature dictate that there should be a cooling demand and the outdoor temperature
is preventing this demand.
D:
R:
55°F
OFF
0 to 80°F
(5°F increments)