Using the Carrier® Connect™ Wi-Fi Thermostat's screens   
 
 
 
 
33CONNECTSTAT43    ©2022 Carrier. 
Installation Guide    All rights reserved. 
  30 
 
Use the following table to determine values for the terminal outputs to the equipment, when specific demands are 
present.  
NOTES 
•  The value of X denotes that the setting may be Off or On, depending on the state of the FAN ON WITH W set 
on advanced SYSTEM SETTINGS screen. 
•   represents Y3, W2, or O/B, based on the item available and selected in HUM/DEHUM OUTPUT 
configuration. See To configure advanced System Settings (page 14). 
 
 
 
 
FAN 
Use this screen to adjust fan operation. The default setting for fan operation is AUTO for both OCCUPIED and 
UNOCCUPIED periods. When operating in AUTO MODE, the fan only runs when there is an active heating or cooling 
demand. When you select ON, the fan runs continuously, except during the BLOWER ON DELAY when a heat cycle 
is starting. There will be a 30-second minimum on/off timer when changing the FAN MODE. 
These selections are not available if the thermostat has been configured for non-programmable operation. 
 CAUTION  The AUTO selection is a violation of the ASHRAE 90.1 and California Title 24, but is a feature of 
the thermostat for building owners that mandate auto fan operation during occupied periods for energy 
conservation purposes.