Appendix: BACnet Points List
33CONNECTSTAT43 ©2022 Carrier.
Installation Guide All rights reserved.
47
Point Name
Point Access
Units
BACnet Point Name
BACnet
Object ID
Indoor Equipment Type
READ_ONLY
1=NO INDOOR
2=FURNACE
3=AIR HANDLER
ID_EQUIP_TYPE
MSV:500
Outdoor Equipment Type
GATED_WRITE
1=NO OUTDOOR
2=A/C
3=HEAT PUMP
OD_EQUIP_TYPE
MSV:501
Remote Sensor Type
GATED_WRITE
1=NONE
2=OUTDOOR
3=SPACE
4=AVERAGE
5=OCCUPANCY
6=FAULT_INPUT
7=SAT
REMOTE_SENSOR
MSV:502
Dehumidification Type
GATED_WRITE
1=NO
2=YES
3=OVRCRL(2F)
4=HUMIDIMIZER
DEHUM_TYPE
MSV:503
Occupancy Output Terminal
GATED_WRITE
1=OFF
2=Y3
3=O/B
4=W2
OCC_OUTPUT
MSV:504
Humidification Output
Terminal
GATED_WRITE
1=OFF
2=Y3
3=O/B
4=W2
HUM_OUTPUT
MSV:505
Dehumidification Output
Terminal
GATED_WRITE
1=OFF
2=Y3
3=O/B
4=W2
DEHUM_OUTPUT
MSV:506
Smart Recovery
GATED_WRITE
1=NO
2=30 MIN
3=60 MIN
4=90 MIN
SMART_RECVRY
MSV:507
General Purpose Output
Timeout
GATED_WRITE
1=2 MIN
2=20 MIN
3=1 HR
4=UNLIMITED
GP_OUT_TIMEOUT
MSV:508
Network GP Y3 Mode
GATED_WRITE
1=DISABLED
2=ENERGIZED_ACTIVE
3=ENERGIZED_INACTIVE
NET_GP_Y3_MODE
MSV:509
Network GP W2 Mode
GATED_WRITE
1=DISABLED
2=ENERGIZED_ACTIVE
3=ENERGIZED_INACTIVE
NET_GP_W2_MODE
MSV:510