35
Table 22 — Service Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
4 Reset Configuration Table (cont) Demand Limit Select
x
0 = None (Default), 1 = Two-step switch,
2 = 4-20 mA, 3 = CCN Loadshed
Loadshed Group Number
x
0-99, Default: 0
Loadshed Demand Delta
xxx%
0-60%, Default: 0
Maximum Loadshed Time
xx min
0-120 min, Default: 60 min
WATER VALVE PID
Proportional PID Gain
x.x
Default = 1.0
Adjustable from -20.0 to 20.0
Integral PID Gain
x.x
Default = 0.1
Adjustable from -20.0 to 20.0
Derivative PID Gain
x.x
Default = 0.0
Adjustable from -20.0 to 20.0
AIR MOTOR MASTER
PID
Proportional PID Gain
x.x
Default = 1.0
Adjustable from -20.0 to 20.0
Integral PID Gain
x.x
Default = 0.1
Adjustable from -20.0 to 20.0
Derivative PID Gain
x.x
Default = 0.0
Adjustable from -20.0 to 20.0
5 Factory Configuration Codes
FACTORY CODES
Configuration Code 1
xxxxxxxx
Factory set. See Table 25.
Configuration Code 2
xxxxxxxx
Factory set. See Table 25.
Configuration Code 3
xxxxxxxx
Factory set. See Table 25.
SERVICE CODES
Configuration Code 4
xxxxxxxx
Factory set. See Table 25.
Configuration Code 5
xxxxxxxx
Factory set. See Table 25.
6 NOT USED
7 Transducer Calibration
CALIBRATION OFFSET See Pressure Transducer Calibration, page 61.
CIRCUIT A PRESSURE
Discharge Pressure
xxx.x PSI
Suction Pressure
xxx.x PSI
A1 Oil Pressure
xxx.x PSI
A2 Oil Pressure
xxx.x PSI
Economizer Pressure
xxx.x PSI
CALIBRATION OFFSET
CIRCUIT B PRESSURE
Discharge Pressure
xxx.x PSI
Suction Pressure
xxx.x PSI
B1 Oil Pressure
xxx.x PSI
B2 Oil Pressure
xxx.x PSI
Economizer Pressure
xxx.x PSI
See Legend on page 36.