47
Table 36 — Alarm and Alert Codes (cont)
ALARM/ALERT
CODE
ALARM OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM GENERATED?
ACTION TAKEN
BY CONTROL
RESET METHOD
PROBABLE
CAUSE
7 Alert Cir. A Discharge Gas 
Thermistor Failure
Thermistor outside 
range of –40 to 245 F 
(–40 to 118 C) or DGT 
> 210 F (98.9 C)
Circuit A shut down Manual Thermistor failure, motor 
cooling solenoid failure 
or wiring error.
8 Alert Cir. B Discharge Gas 
Thermistor Failure
Thermistor outside 
range of –40 to 245 F 
(–40 to 118 C) or DGT 
> 210 F (98.9 C)
Circuit B shut down Manual Thermistor failure, motor 
cooling solenoid failure 
or wiring error.
9 Alarm Cooler Leaving Fluid 
Thermistor Failure
Thermistor outside 
range of –40 to 245 F 
(–40 to 118 C)
Chiller shut down Automatic Thermistor failure, dam-
aged cable/wire or wir-
ing error.
10 Alarm Cooler Entering Fluid 
Thermistor Failure
Thermistor outside 
range of –40 to 245 F 
(–40 to 118 C)
Uses 0.1° F/% Total 
Capacity as rise/ton
Automatic Thermistor failure, dam-
aged cable/wire or wir-
ing error.
11 Alert Condenser Leaving 
Fluid Thermistor Failure
Thermistor outside 
range of –40 to 245 F 
(–40 to 118 C)
None. Chiller continues 
to run.
Automatic Thermistor failure, dam-
aged cable/wire or wir-
ing error.
12 Alert Condenser Entering 
Fluid Thermistor Failure
Thermistor outside 
range of –40 to 245 F 
(–40 to 118 C)
None. Chiller continues 
to run.
Automatic Thermistor failure, dam-
aged cable/wire or wir-
ing error.
15 Alert Compressor A1 High 
Motor Temperature
Thermistor outside 
range of –39.9 to 245 F 
(–39.9 to 118 C) for 5 
consecutive readings
Compressor A1 shut 
down
Manual Thermistor failure, motor 
cooling (all), or Econo-
mizer (2 comp. circuits) 
solenoid failure.
16 Alert Compressor A2 High 
Motor Temperature
Thermistor outside 
range of –39.9 to 245 F 
(–39.9 to 118 C) for 5 
consecutive readings
Compressor A2 shut 
down
Manual Thermistor failure, motor 
cooling (all), or Econo-
mizer (2 comp. circuits) 
solenoid failure.
17 Alert Compressor B1 High 
Motor Temperature
Thermistor outside 
range of –39.9 to 245 F 
(–39.9 to 118 C) for 5 
consecutive readings
Compressor B1 shut 
down
Manual Thermistor failure, motor 
cooling (all), or Econo-
mizer (2 comp. circuits) 
solenoid failure.
18 Alert Compressor B2 High 
Motor Temperature
Thermistor outside 
range of –39.9 to 245 F 
(–39.9 to 118 C) for 5 
consecutive readings
Compressor B2 shut 
down
Manual Thermistor failure, motor 
cooling (all), or Econo-
mizer (2 comp. circuits) 
solenoid failure.
21 Alert External Reset Temper-
ature Thermistor Failure
Thermistor outside 
range of –40 to 245 F 
(–40 to 118 C)
Reset disabled. Runs 
under normal control/set 
points.
Automatic Thermistor failure or wir-
ing error.
22 Alert Circuit A Discharge 
Pressure Transducer 
Failure
Calibration offset more 
than 6 PSIG (41 kPa) or 
Voltage ratio (volts read/
ref. voltage) more than 
99.9% or less than 0.5%
Circuit A shut down Automatic Transducer failure, 
power supply failure, or 
wiring damage/error.
23 Alert Circuit B Discharge 
Pressure Transducer 
Failure
Calibration offset more 
than 6 PSIG (41 kPa) or 
Voltage ratio (volts read/
ref. voltage) more than 
99.9% or less than 0.5%
Circuit B shut down Automatic Transducer failure, 
power supply failure, or 
wiring damage/error.
24 Alert Circuit A Suction 
Pressure Transducer 
Failure
Calibration offset more 
than 6 PSIG (41 kPa) or 
Voltage ratio (volts read/
ref. voltage) more than 
99.9% or less than 0.5%
Circuit A shut down Automatic Transducer failure, 
power supply failure, or 
wiring damage/error.
25 Alert Circuit B Suction 
Pressure Transducer 
Failure
Calibration offset more 
than 6 PSIG (41 kPa) or 
Voltage ratio (volts read/
ref. voltage) more than 
99.9% or less than 0.5%
Circuit B shut down Automatic Transducer failure, 
power supply failure, or 
wiring damage/error.
26 Alert Comp A1 Oil Pressure 
Transducer Failure
Calibration offset more 
than 6 PSIG (41 kPa) or 
Voltage ratio (volts read/
ref. voltage) more than 
99.9% or less than 0.5%
Comp A1 shut down Automatic Transducer failure, 
power supply failure, or 
wiring damage/error.
27 Alert Comp A2 Oil Pressure 
Transducer Failure
Calibration offset more 
than 6 PSIG (41 kPa) or 
Voltage ratio (volts read/
ref. voltage) more than 
99.9% or less than 0.5%
Comp A2 shut down Automatic Transducer failure, 
power supply failure, or 
wiring damage/error.
28 Alert Comp B1 Oil Pressure 
Transducer Failure
Calibration offset more 
than 6 PSIG (41 kPa) or 
Voltage ratio (volts read/
ref. voltage) more than 
99.9% or less than 0.5%
Comp B1 shut down Automatic Transducer failure, 
power supply failure, or 
wiring damage/error.
29 Alert Comp B2 Oil Pressure 
Transducer Failure
Calibration offset more 
than 6 PSIG (41 kPa) or 
Voltage ratio (volts read/
ref. voltage) more than 
99.9% or less than 0.5%
Comp B2 shut down Automatic Transducer failure, 
power supply failure, or 
wiring damage/error.
30 Alert Circuit A Economizer 
Transducer Failure
Calibration offset more 
than 6 PSIG (41 kPa) or 
Voltage ratio (volts read/
ref. voltage) more than 
99.9% or less than 0.5%
Circuit A shut down Automatic Transducer failure, 
power supply failure, or 
wiring damage/error.