71
RELAY BOARD 1
K3
T4
T3
BLK
BLK
TB2
TB2
4
5
C1
C2
EQUIP GND
SEPARATE
115 OR 230 V
FIELD POWER
SUPPLY
CWP
SEPARATE
115 OR 230 V
FIELD POWER
SUPPLY
K3
RELAY BOARD 1
EQUIP GND
C2C1
T3
T4
CWP
MAX. LOAD ALLOWED FOR THE CWP RELAY IS
125 VA SEALED, 1250 VA INRUSH AT 115 OR 230 VOLT.
MIN. LOAD 10 VA SEALED.
ACCESSORY ONLY
Fig. 29 — Chilled Water Pump Relay Wiring; 30HXA,C
MAX. LOAD ALLOWED FOR THE CWP RELAY IS
125 VA SEALED, 1250 VA INRUSH AT 115 OR 230 VOLT.
MIN. LOAD 10 VA SEALED.
ACCESSORY ONLY
Fig. 30 — Chilled Water Pump Relay Wiring; 30GX