Evaporator CPR Adjustment  
D 
* The CPR adjustment must be INCREASED by approximately +0.5 psi for 
every additional foot (+0.1 bar per meter) that the evaporator is located 
(distance D minus 6”) from the front wall of the vehicle. 
When the setting has been adjusted, tighten the 
jam nut securely against the setting screw to 
prevent any vibration of the set screw (and to 
prevent disruption of the CPR setting). 
Replace the CPR cap and remove gauges. 
MODEL  CPR Setting at CPR Port 
 
 
PSI     BAR 
Neos 100S  10.3 psi  .7 bar 
20X  27.5 psi  1.9 bar 
30S*  18.9 psi  1.3 bar 
35X  30.5 psi  2.1 bar 
40X  33.4 psi  2.3 bar 
50X  37.7 psi  2.6 bar 
*Only the 115V standby version of the 30S has a CPR.  
No other 30S versions require adjustment.