Installation & Commissioning Manual:
Neos 100S, 20X, 30S, 35X, 40X, 50X
62-11165 Rev D
®
27
Evaporator CPR Adjustment
D
* The CPR adjustment must be INCREASED by approximately +0.5 psi for
every additional foot (+0.1 bar per meter) that the evaporator is located
(distance D minus 6”) from the front wall of the vehicle.
When the setting has been adjusted, tighten the
jam nut securely against the setting screw to
prevent any vibration of the set screw (and to
prevent disruption of the CPR setting).
Replace the CPR cap and remove gauges.
MODEL CPR Setting at CPR Port
PSI BAR
Neos 100S 10.3 psi .7 bar
20X 27.5 psi 1.9 bar
30S* 18.9 psi 1.3 bar
35X 30.5 psi 2.1 bar
40X 33.4 psi 2.3 bar
50X 37.7 psi 2.6 bar
*Only the 115V standby version of the 30S has a CPR.
No other 30S versions require adjustment.