5.4  Size of joint pipes for outdoor unit
Base on the following tables, select the diameters of the outdoor 
unit connective pipes. In case of the main accessory pipe large 
than the main pipe, take the large one for the selection.
Example: parallel connect with the three outdoor units 16+16+14 
(the total capacity is 46HP), all indoor units total capacity is 1360, 
provided that the equivalent length of all pipes are ≥90m, accord-
ing to the Table5-5 the main pipe diameter areΦ38.1/Φ22.2; in 
according to all indoor unit capacity 1360, we could find out the 
master unit diameter isΦ41.3/Φ22.2 base on Table.5-3. Take the 
large one for the selection, we final confirm the main pipe diameter 
is Φ41.3/Φ22.2.
Model
Gas side Liquid side
Φ22.2
Φ22.2
Φ25.4
Φ28.6
Φ28.6
Φ28.6
Φ31.8
Φ41.2
Φ9.53
Φ9.53
Φ12.7
Φ12.7
Φ15.9
Φ15.9
Φ19.1
Φ22.2
 When the equivalent length of all liquid 
pipes < 90m, the size of main pipe(mm)
8HP
10HP
12~14HP
  16HP
18~22HP
24HP
26~32HP
50~64HP
Φ38.1
Φ19.1
34~48HP
Size of joint pipes for 410A outdoor unit
Table.5-4
BJF-330-CM(i)
BJF-330-CM(i)
BJF-330-CM(i)
BJF-710-CM(i)
BJF-710-CM(i)
BJF-710-CM(i)
BJF-710-CM(i)
BJF-1344-CM(i)
BJF-E1344-CM(i)
Model
Gas side Liquid side
Φ22.2
Φ25.4
Φ28.6
Φ31.8
Φ31.8
Φ31.8
Φ38.1
Φ44.5
Φ12.7
Φ12.7
Φ15.9
Φ15.9
Φ19.1
Φ19.1
Φ22.2
Φ25.4
 When the equivalent length of all liquid 
pipes ≥ 90m, the size of main pipe(mm)
8HP
10HP
12~14HP
   16HP
18~22HP
24HP
26~32HP
50~64HP
Φ38.1
Φ22.2
34~48HP
Size of joint pipes for 410A outdoor unit
Table.5-5
BJF-330-CM(i)
BJF-330-CM(i)
BJF-710-CM(i)
BJF-710-CM(i)
BJF-710-CM(i)
BJF-710-CM(i)
BJF-1344-CM(i)
BJF-1344-CM(i)
BJF-E1344-CM(i)
  The 1st
 
branch joint
  The 1st
 
branch joint
5.5  Branch pipes for outdoor unit
Table.5-6
5.6  Branch pipes for indoor unit
8HP, 10HP
12HP, 14HP, 16HP
Model
Φ25.4 Φ12.7
Φ31.8 Φ15.9
Gas side
Liquid side
Outdoor unit pipe connective 
opening dimension(mm)
Base on Table.5-7 and Table.5-8 select the multi connecting pipes 
of outdoor unit. Before installation, please read the Outdoor Unit 
branch joint Installation Manual carefully. 
Table.5-7 Outdoor unit multi-connective pipe assembly (Illustration)
Main pipe
g1, g2
8, 10HPΦ25.4/Φ12.7;
12~18HP: Φ31.8/Φ15.9
L:
BJC-02-CM(i)
L+M:
BJC-03-CM(i)
L+M+N:
BJC-04-CM(i)
g1, g2, g3:
8, 10HP: Φ25.4/Φ12.7;
12~18HP: Φ31.8/Φ15.9;
G1: Φ38.1/Φ19.1
g1, g2, g3, g4:
8, 10HP: Φ25.4/Φ12.7;
12~18HP: Φ31.8/Φ15.9;
G1: Φ38.1/Φ19.1;
G2: Φ41.3/Φ22.2
Illustration
Outdoor 
unit Qty.
2 units
3 units
4 units
Main pipe
Table.5-8 Outdoor unit multi-connective pipe assembly
Outdoor 
unit Qty.
2 units
3 units
4 units
Outdoor unit connective 
pipe diameter
Parallel connect 
with the branch 
joint assembly
Refer to 
Table. 5-4 
or 5-5 for 
main pipe 
dimension
Note: The pipe assemblies in above table is special for this model, 
must be purchased separately.
/
JJ
/
0
JJ
*
J
Main pipe
/
0
1
*
*
JJJJ
Main pipe
Φ44.5
Φ25.4
66~72HP BJF-E1344-CM(i)
Φ54.0
Φ25.4
66~72HP BJF-E1500-CM(i)
18HP
Φ31.8
Φ19.1