EasyManua.ls Logo

Carrier S-Series - Gas Tightness Testing Procedure

Carrier S-Series
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
Installation manual
Unit: mm
5.7 Example
Liquid side
Gas side
Liquid side
Gas side
Indoor unit
capacity
A(×100W)
A≤45
A≥56
Φ12.7 Φ6.4
Φ15.9 Φ9.5 Φ19.1
Φ12.7
Φ15.9 Φ9.5
Table.5-9
Take (16+12+10) HP that composed by three modules as an
example to clarify the pipe selection.
Take Fig.5-4 as an example. Provided that the equivalent
length of all pipes in this system is larger than 90m.
When branch joint’s
length ŏ10m
When branch joint’s
length˚10m
1)
2)
Parallel connect the outdoor units
The outdoor unit linked by Pipe g1 is 10HP, parallel connects with
outdoor unit. refer to Table.5-8 the connective pipe diameter is
Φ25.4/Φ12.7;
The outdoor unit linked by Pipe g2 is 12HP, parallel connects with
outdoor unit.refer to Table.5-8 the connective pipe diameter is
Φ31.8/Φ15.9;
The outdoor unit linked by Pipe g3 is 16HP, parallel connects with
outdoor unit. refer to Table.5-8 the connective pipe diameter is
Φ31.8/Φ15.9.
The upstream of G1 is the two parallel connected outdoor units,
refer to Table.5-8 select the three parallel connected outdoor unit,
the pipe diameter isΦ38.1/Φ19.1.
Parallel connect the three outdoor units, refer to Table.5-8 should
select BJC-03-CM(i) for outdoor unit connective pipes (L+M).
D
1)
2)
3)
The main pipe L9 with N9, N10 downstream indoor units that total
capacity is 56+56=112, the pipe L9 diameter is Φ15.9/Φ9.5, thus
select BJF-224-CM(i) for the branch joint I.
The main pipe L8 with N8ЊN10 downstream indoor units that total
capacity is 140+56+56=252, the pipe L8 diameter is Φ22.2/Φ9.5,
thus select BJF-330-CM(i) for the branch joint H.
The main pipe L5 with N5ЊN10 downstream indoor units that total
capacity is 140×2+56×2+71×2=534, the pipe L5 diameter is Φ
28.6/Φ15.9, thus select BJF-710-CM(i) for the branch joint E.
The main pipe A with N1ЊN10 downstream indoor units that total
capacity is 140×6+56×2+71×2ω1094, thus select BJF-1344-
CM(i. for the branch joint A.
Main pipe (Refer to Table.5-3, Table.5-5):
Main pipe L1 in the Fig.5-4, which upstream outdoor units total
capacity is 10+12+16ω38, base on table.5-5, the gas/liquid pipe
diameter are Φ38.1/Φ19.1, total capacity of the downstream
indoor unit is 140×6+56×2+71×2ω1094, base on table.5-3, the
gas/liquid pipe diameter are Φ38.1/Φ19.1, take the large one for
your selection, final confirm the main pipe diameter is: gas/liquid
pipe Φ38.1/Φ22.2.
The branch joint at the inside of the unit.
There are a~j branch joints at the inside of the unit, the branch
joint diameter should be select as per Table. 5-9.
Main pipe at the inside the unit (Refer to Table. 5-3)
The main pipe L3 with N1, N2 downstream indoor units that
total capacity is 140×2=280, the pipe L3 diameter is Φ22.2/Φ
9.5, thus select BJF-330-CM(i) for the branch joint C.
The main pipe L4 with N3, N4 downstream indoor units that
total capacity is 140×2=280, the pipe L4 diameter is Φ22.2/Φ
9.5, thus select BJF-330-CM(i) for the branch joint D.
The main pipe L2 with N1~N4 downstream indoor units that
total capacity is 140×4=560, the pipe L2 diameter is Φ28.6/Φ
15.9, thus select BJF-710-CM(i) for the branch joint B.
The main pipe L7 with N6, N7 downstream indoor units that
total capacity is 71×2=142, the pipe L7 diameter is Φ15.9/Φ
9.5, thus select BJF-224-CM(i) for the branch joint G.
The main pipe L6 with N5ЊN7 downstream indoor units that
total capacity is 140+71×2=282, the pipe L6 diameter is Φ22.2/
Φ9.5, thus select BJF-330-CM(i) for the branch joint F.
A
B
1)
2)
3)
4)
5)
6)
7)
8)
9)
C
N1
(140)
N3
(140)
N5
(140)
N6
(71)
N7
(71)
N9
(56)
N8
(140)
N2
(140)
N4
(140)
N10
(56)
$
B
(
F
H
G
I
C
D
L1
L2
L3
L4
L5
L6
L8
L9
L7
ab
c
d
ef
g
i
j
h
W3
(10)
W2
(12)
W1
(16)
0
/
g1 g2 g3
G1
Fig.5-4
Quantity setting
dial switch of
indoor units
Constraint
cooling
Query button
Outdoor address
dial switch
Outdoor power
dial switch

Related product manuals