The following table has columns for Code and English displays. English is
the default setting. Change Functional Parameter to Code to see Code
display format.
Table notes:
•
+ = Unit Shutdown
• = Can Be Configured To Shut Down
• = Fault Light On
CODE ENGLISH DESCRIPTION
AL0 ENG OIL
+ Low Oil Pressure
AL1 ENG HOT
+ High Coolant Temperature
AL2 HI PRESS
+ High Pressure
AL3 STARTFAIL
+ Auto Start Failure
AL4 LOW BATT
+ Low Battery Voltage
AL5 HI BATT
+ High Battery Voltage
AL6 DEFR FAIL Defrost Override
AL7 ALT AUX No Alternator Auxiliary Output
AL8 STARTER Starter Motor Fault
AL9 RA SENSOR Return Air Sensor Fault
AL10 SA SENSOR Supply Air Sensor Fault
AL11 WT SENSOR
Coolant Temperature Sensor
Fault
AL12 HIGH CDT
+ When
temp ex-
ceeds 350°
High Discharge Temperature
AL13 CD SENSOR Discharge Temp Sensor Fault