11

No. Unit  
1 °C Cooler Entering Fluid Evaporator entering water temperature
2 °C Cooler Leaving Fluid Evaporator leaving water temperature
3 °C Condenser Entering Fluid Condenser entering water temperature
4 °C Condenser Leaving Fluid Condenser leaving water temperature
5 °C Saturated Cond Tmp cir A Saturated condensing temperature, circuit A
6 °C Saturated Suction Temp A Saturated suction temperature, circuit A
7 °C Compressor Suction Tmp A Suction temperature, circuit A
8 °C Discharge Gas Temp cir A Discharge gas temperature, circuit A
9 °C Motor Temperature cir A Motor temperature, circuit A
10 °C Saturated Cond Tmp cir B Saturated condensing temperature, circuit B
11 °C Saturated Suction Temp B Saturated suction temperature, circuit B
12 °C Compressor Suction Tmp B Suction temperature, circuit B
13 °C Discharge Gas Temp cir B Discharge gas temperature, circuit B
14 °C Motor Temperature cir B Motor temperature, circuit B
15 °C Optional Space Temp Optional space temperature
16 °C CHWS Temperature Master/slave temperature
17 °C CHWS Heat Temp Master/slave heating temperature
18 °C Dry Cool Leav Water Tmp Dry cooler - leaving water temperature
19 °C External Temperature External temperature (dry cooler OAT)
Associated table: 
No. Unit  
1 kPa Discharge Pressure A Discharge gas pressure, circuit A
2 kPa Main Suction Pressure A Suction gas pressure, circuit A
3 kPa Oil Pressure A Oil pressure, circuit A
4 kPa Oil Pressure Di erence A Oil pressure di erence, circuit A
5 kPa Discharge Pressure B Discharge gas pressure, circuit B
6 kPa Main Suction Pressure B Suction gas pressure, circuit B
7 kPa Oil Pressure B Oil pressure, circuit B
8 kPa Oil Pressure Di erence B Oil pressure di erence, circuit B
Associated table:  - 
No. Status Unit  
1 open/closed - Remote On/O Switch Remote On/O Switch
2 open/closed - Remote HeatCool Switch Heating/cooling selection switch
3 open/closed - Remote Setpoint Switch Setpoint selection switch
4 open/closed - Limit Switch 1 Capacity limitation switch 1
5 open/closed - Limit Switch 2 Capacity limitation switch 2
6 open/closed - Oil Level Input A Oil level input, circuit A
7 open/closed - Oil Level Input B Oil level input, circuit B
8 - mA Reset/Setpnt4-20mA Sgnl 4-20 mA signal, setpoint reset
9 - mA Limit 4-20mA Signal 4-20 mA signal, capacity limitation
10 - V Leakage detector 1 val Leak detection input 1
11 - V Leakage detector 2 val Leak detection input 2
12 open/closed - Customer Interlock Customer interlock status
13 open/closed - Ice Done Storage Switch Ice storage end switch
14 open/closed - Occupied Override Switch Occupied override switch
15 no/yes - BACnet Dongle BACnet dongle
Associated table: 
No. Status Unit  
1 on/o - Compressor A Output, compressor A
2 on/o - Oil Solenoid Output A Oil solenoid output, circuit A
3 on/o - Slide Valve 1 Output A Slide valve 1 output, circuit A
4 on/o - Slide Valve 1 Output A Slide valve 2 output, circuit A
5 - Volt Capacity Signal Cir A 0-10 V signal, capacity circuit A
6 on/o - Compressor B Output, compressor B
7 on/o - Oil Solenoid Output B Oil solenoid output, circuit B
8 on/o - Slide Valve 1 Output B Slide valve 1 output, circuit B
9 on/o - Slide Valve 1 Output B Slide valve 2 output, circuit B
10 Volt Capacity Signal Cir B 0-10 V signal, capacity circuit B
11 Volt Chiller Capacity signal Chiller capacity signal
12 on/o - Alarm Relay Status Alarm status
13 on/o - Running Relay Status Run status
14 on/o Alert Relay Status Alert status
15 on/o - Shutdown Indicator Status Shutdown status
16 0 to 100 % Cond 3 Way Valve Pos Position of three-way valve
17 on/o - Drycooler Fan 1 Output, dry cooler 1
18 on/o - Drycooler Fan 2 Output, dry cooler 2
19 on/o - Drycooler Fan 3 Output, dry cooler 3
20 on/o - Drycooler Fan 4 Output, dry cooler 4
21 on/o - Drycooler Fan 5 Output, dry cooler 5
* Depends on selected language, default is English