Carrier Touch Pilot 30XW-V - Pump, Mode, and Setpoint Table Configuration

Carrier Touch Pilot 30XW-V
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
Associated table: 
No. Status Unit  
1 yes/no - Cooler Flow Setpoint Out Evaporator  ow setpoint output
2 on/o - Cooler Pump #1 Command Evaporator pump control 1
3 on/o - Cooler Pump #2 Command Evaporator pump control 2
4 on/o - Rotate Cooler Pumps ? Evaporator pump rotation?
5 open/closed - Cooler Flow Switch Flow switch
6 on/o - Condenser Pump Command1 Condenser pump control 1
7 on/o - Condenser Pump Command2 Condenser pump control 2
8 on/o - Rotate Condenser Pumps ? Condenser pump rotation?
9 open/closed - Condenser Flow Status Condenser  ow status
Run times
No. Status Unit  
1 - hour Machine Operating Hours Unit operating hours
2 - - Machine Starts Number Number of unit starts
3 - hour Compressor A Hours Operating hours, compressor A
4 - - Compressor A Starts Number of starts, compressor A
5 - hour Compressor B Hours Operating hours, compressor B
6 - - Compressor B Starts Number of starts, compressor B
7 - hour Cooler Pump #1 Hours Operating hours, evaporator pump 1
8 - hour Cooler Pump #2 Hours Operating hours, evaporator pump 2
9 - hour Condenser Pump #1 Hours Operating hours, condenser pump 1
10 - hour Condenser Pump #2 Hours Operating hours, condenser pump 2

No. Status Unit  
1 yes/no - Start-up delay in e ect Start-up delay in e ect
2 yes/no - Second Setpoint in Use Second setpoint in use
3 yes/no - Reset in e ect Setpoint reset active
4 yes/no - Demand limit active Demand limit active
5 yes/no - Cooler Pump Rotation Evaporator pump rotation
6 yes/no - Pump Periodic Start Periodic pump start-up
7 yes/no - Night Low Noise Active Night mode active
8 yes/no - Master Slave Active Master/slave active
9 yes/no - Auto Changeover Active Automatic changeover active
10 yes/no - Condenser Pump Rotation Condenser pump rotation
11 yes/no - Cond Pump Periodic Start Periodic condenser pump start-up
12 yes/no - Ice Mode in E ect Ice storage mode active

No. Status  Unit  
1 -28.9 to 26.0 6.7 °C Cooling Setpoint 1 Cooling setpoint 1
2 -28.9 to 26.0 6.7 °C Cooling Setpoint 2 Cooling setpoint 2
3 -28.9 to 26.0 6.7 °C Cooling Ice Setpoint Ice storage setpoint
4 0.1 to 11.1 0.6 ^C Cooling Ramp Loading Cooling ramp loading
5 26.7 to 63.0 37.8 °C Heating Setpoint 1 Heating setpoint 1
6 26.7 to 63.0 37.8 °C Heating Setpoint 2 Heating setpoint 2
7 0.1 to 11.1 0.6 ^C Heating Ramp Loading Heating ramp loading
8 3.9 to 50.0 23.9 °C Cool Changeover Setpt Auto changeover setpoint, cooling
9 0 to 46.1 17.8 °C Heat Changeover Setpt Auto changeover setpoint, heating
10 26.7 to 48.9 35.0 °C Water Val Condensing Stp Water valve condensing setpoint
11 0 to 100 100 % Switch Limit Setpoint 1 Limit setpoint switch 1
12 0 to 100 100 % Switch Limit Setpoint 2 Limit setpoint switch 2
13 0 to 100 100 % Switch Limit Setpoint 3 Limit setpoint switch 3
* Depends on selected language, default is English
No. Status Unit  
22 on/o - Drycooler Fan 6 Output, dry cooler 6
23 on/o - Drycooler Fan 7 Output, dry cooler 7
24 on/o - Drycooler Fan 8 Output, dry cooler 8
25 0 to 10 V Dry Cool Vfan 1 Output Dry Cooler variable speed fan 1 output