Pump Conguration Menu – PUMPCONF
No. Name Status Default Unit Displayed text * Description
1 hpumpseq 0 to 1 0 - Condenser Pumps
Sequence
Condenser pumps sequence
2 cpumpseq 0 to 1 0 - Cooler Pumps Sequence Cooler pumps sequence
3 0 = No Pump 0 = no pump
4 1 = One Pump Only 1 = one pump only
5 pump_per no/yes no - Pump Sticking Protection Pump anti-sticking protection
6 pump_sby no/yes no - Stop Pump During Standby Pump stopped during standby
7 pump_loc no/yes yes - Flow Checked If Pump Off Water ow is checked when the pump is off
8 stopheat no/yes no - Cooler Pump Off In Heat Cooler pump is off when the unit is in Heating
9 stopcool no/yes no - Cond Pump Off In Cool Condenser pump is off when the unit is in Cooling
*Displayed in English by default.
Reset Conguration Menu – RESETCFG
No. Name Status Default Unit Displayed text * Description
1 cr_sel 0 to 4 0 - Cooling Reset Select Reset source in Cooling
2 hr_sel 0 to 4 0 - Heating Reset Select Reset source in Heating
3 0=None, 1=OAT 0 = None
1 = OAT
4 2=Delta T, 4=Space Temp 2 = Delta T
4 = Space temperature
5 3=4-20mA control 3 = 4-20 mA signal
6
7 Cooling Cooling
8 oat_crno -10 to 51.7
14 to 125
-10
14
°C
°F
OAT No Reset Value OAT, no reset value
(applies to units with a Dry Cooler at the condenser)
9 oat_crfu -10 to 51.7
14 to 125
-10
14
°C
°F
OAT Full Reset Value OAT, max. reset value
(applies to units with a Dry Cooler at the condenser)
10 dt_cr_no 0 to 13.9
0 to 25
0
0
^C
^F
Delta T No Reset Value Delta T, no reset value
11 dt_cr_fu 0 to 13.9
0 to 25
0
0
^C
^F
Delta T Full Reset Value Delta T, max. reset value
12 v_cr_no 0 to 20 0 mA Current No Reset Value Current, no reset value
13 v_cr_fu 0 to 20 0 mA Current Full Reset Value Current, max. reset value
14 spacr_no -10 to 51.7
14 to 125
-10
14
°C
°F
Space T No Reset Value Space temperature, no reset value
15 spacr_fu -10 to 51.7
14 to 125
-10
14
°C
°F
Space T Full Reset Value Space temperature, max. reset value
16 cr_deg -16.7 to 16.7
-30 to 30
0
0
^C
^F
Cooling Reset Deg. Value Cooling reset value
17
18 Heating Heating
19 oat_hrno -10 to 51.7
14 to 125
-10
14
°C
°F
OAT No Reset Value OAT, no reset value
(applies to units with a DryCooler at the condenser)
20 oat_hrfu -10 to 51.7
14 to 125
-10
14
°C
°F
OAT Full Reset Value OAT, max. reset value
(applies to units with a DryCooler at the condenser)
21 dt_hr_no 0 to 13.9
0 to 25
0
0
^C
^F
Delta T No Reset Value Delta T, no reset value
22 dt_hr_fu 0 to 13.9
0 to 25
0
0
^C
^F
Delta T Full Reset Value Delta T, max. reset value
23 v_hr_no 0 to 20 0 mA Current No Reset Value Current, no reset value
24 v_hr_fu 0 to 20 0 mA Current Full Reset Value Current, max. reset value
25 spahr_no -10 to 51.7
14 to 125
-10
14
°C
°F
Space T No Reset Value Space temperature, no reset value
26 spahr_fu -10 to 51.7
14 to 125
-10
14
°C
°F
Space T Full Reset Value Space temperature, max. reset value
27 hr_deg -16.7 to 16.7
-30 to 30
0
0
^C
^F
Heating Reset Deg. Value Heating reset value
*Displayed in English by default.