Pump Conguration Menu – PUMPCONF
No. Name Status Default Unit Displayed text * Description
1 hpumpseq 0 to 1 0 - Condenser Pumps
Sequence
Condenser pumps sequence
2 cpumpseq 0 to 1 0 - Cooler Pumps Sequence Cooler pumps sequence
3 0 = No Pump 0 = no pump
4 1 = One Pump Only 1 = one pump only
5 pump_per no/yes no - Pump Sticking Protection Pump anti-sticking protection
6 pump_sby no/yes no - Stop Pump During Standby Pump stopped during standby
7 pump_loc no/yes yes - Flow Checked If Pump Off Water ow is checked when the pump is off
8 stopheat no/yes no - Cooler Pump Off In Heat Cooler pump is off when the unit is in Heating
9 stopcool no/yes no - Cond Pump Off In Cool Condenser pump is off when the unit is in Cooling
*Displayed in English by default.
Reset Conguration Menu – RESETCFG
No. Name Status Default Unit Displayed text * Description
1 cr_sel 0 to 4 0 - Cooling Reset Select Reset source in Cooling
2 hr_sel 0 to 4 0 - Heating Reset Select Reset source in Heating
3 0=None, 1=OAT 0 = None
1 = OAT
4 2=Delta T, 4=Space Temp 2 = Delta T
4 = Space temperature
5 3=4-20mA control 3 = 4-20 mA signal
6
7 Cooling Cooling
8 oat_crno -10 to 51.7
14 to 125
-10
14
°C
°F
OAT No Reset Value OAT, no reset value
(applies to units with a Dry Cooler at the condenser)
9 oat_crfu -10 to 51.7
14 to 125
-10
14
°C
°F
OAT Full Reset Value OAT, max. reset value
(applies to units with a Dry Cooler at the condenser)
10 dt_cr_no 0 to 13.9
0 to 25
0
0
^C
^F
Delta T No Reset Value Delta T, no reset value
11 dt_cr_fu 0 to 13.9
0 to 25
0
0
^C
^F
Delta T Full Reset Value Delta T, max. reset value
12 v_cr_no 0 to 20 0 mA Current No Reset Value Current, no reset value
13 v_cr_fu 0 to 20 0 mA Current Full Reset Value Current, max. reset value
14 spacr_no -10 to 51.7
14 to 125
-10
14
°C
°F
Space T No Reset Value Space temperature, no reset value
15 spacr_fu -10 to 51.7
14 to 125
-10
14
°C
°F
Space T Full Reset Value Space temperature, max. reset value
16 cr_deg -16.7 to 16.7
-30 to 30
0
0
^C
^F
Cooling Reset Deg. Value Cooling reset value
17
18 Heating Heating
19 oat_hrno -10 to 51.7
14 to 125
-10
14
°C
°F
OAT No Reset Value OAT, no reset value
(applies to units with a DryCooler at the condenser)
20 oat_hrfu -10 to 51.7
14 to 125
-10
14
°C
°F
OAT Full Reset Value OAT, max. reset value
(applies to units with a DryCooler at the condenser)
21 dt_hr_no 0 to 13.9
0 to 25
0
0
^C
^F
Delta T No Reset Value Delta T, no reset value
22 dt_hr_fu 0 to 13.9
0 to 25
0
0
^C
^F
Delta T Full Reset Value Delta T, max. reset value
23 v_hr_no 0 to 20 0 mA Current No Reset Value Current, no reset value
24 v_hr_fu 0 to 20 0 mA Current Full Reset Value Current, max. reset value
25 spahr_no -10 to 51.7
14 to 125
-10
14
°C
°F
Space T No Reset Value Space temperature, no reset value
26 spahr_fu -10 to 51.7
14 to 125
-10
14
°C
°F
Space T Full Reset Value Space temperature, max. reset value
27 hr_deg -16.7 to 16.7
-30 to 30
0
0
^C
^F
Heating Reset Deg. Value Heating reset value
*Displayed in English by default.
7 - DETAILED MENU STRUCTURE
23

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier Touch Pilot Control Series and is the answer not in the manual?

Carrier Touch Pilot Control Series Specifications

General IconGeneral
BrandCarrier
ModelTouch Pilot Control Series
CategoryChiller
LanguageEnglish

Related product manuals