8.14 - BACnet (option 149)
The BACnet/IP communication protocol is used by the building 
management system or the programmable controllers to 
communicate with the Touch Pilot interface. It is activated if the 
optional BACnet activation key (dongle) is present on the electronic 
control board. 
This option may be ordered and installed on site. The BACnet 
prole of the Touch Pilot interface is B-ASC. 
For more information about BACnet, please refer to the BACnet 
document included with the control or contact Manufacturer 
Service Agency.
8.15 - Dry cooler (option 154)
19PV units have been specially designed to optimise the operation 
of split installations, using air-cooled condensers as the chiller heat 
rejection system. 
19PV units can control a Carrier dry cooler to cool down the 
condenser water loop. This air exchanger includes all compatible 
control electronics.
8.15.1 - Condensing pressure control
The  control  conguration of  this  functionality  must  be  done by 
a specially trained and qualified engineer during the unit 
installation. The Manufacturer supplies specic documentation for 
this operation to the trained engineers.
The Touch Pilot control system includes logic to permit the control 
of different xed and variable-speed fan variants. 
Touch Pilot continuously optimizes system operation to obtain the 
best system efciency by controlling the number of fans required 
for any thermal load and outside temperature conditions.
8.15.2 - Condensing setpoint
The condensing setpoint is adjustable in the Setpoint menu 
(SETPOINT). 
Condensing setpoint
Minimum value 27°C
Default value 35°C
Maximum value 49°C
The condensing setpoint can be reset by reference to the outside 
temperature to optimize the operation of the condensing system.
To set the condensing setpoint reset, the following adjustments 
are necessary:
 - hr_sel (Heating Reset Select) set to “1” (OAT) in the Reset 
Conguration menu (RESETCFG).
 - oat_crno (OAT no reset value), oat_crfu (OAT full reset value) 
and hr_deg (heating reset degree value) must be set in the 
Reset Conguration menu (RESETCFG). See also section 
8.4.2 for more information about reset control.
8.16 - Dry cooler free cooling (option 313)
19PV units may come with the free cooling option that enables 
the control of a Carrier dry cooler. The chiller and the dry cooler 
have to be connected through a LEN RS-485.
Units tted with a dry cooler provide the “free cooling” functionality 
which means that the chilled water system directly exchanges 
heat using the air-to-water heat exchanger (“dry cooler”). 
For chillers with this option, the Touch Pilot control may use low 
outside air temperature to cool down the water loop and satisfy 
the cooling demand.
The dry cooler is used not only to assist in producing cooling water 
to meet the current cooling demand but it also allows for reducing 
energy consumption.
The dry cooler comes with up to 20 fans, i.e. xed-speed or variable-
speed fans, which can be installed in different congurations. The 
Touch Pilot control distinguishes between two types of fan control 
for a dry cooler free cooling option, where the rst one embraces 
the use of fan staging and the second one includes the use of 
variable-speed fans. Mixed conguration can also be used (xed 
and variable-speed fan control at the same time).
8.17 - Master/Slave control 
The control system allows for master/slave control of two units 
linked by the network. The master unit can be controlled locally, 
remotely or by network commands, while the slave unit remains 
in Network mode.
All control commands to the master/slave assembly (start/stop, 
setpoint selection, heating/cooling control, load shedding, etc.) 
are handled by the unit which is configured as the master. 
The commands are transmitted automatically to the slave unit.
If the master chiller is turned off, while the master/slave function 
is active, then the slave chiller will be stopped. Under certain 
circumstances, the slave unit may be started rst to ensure that 
the run times of the two units are equalised.
In the event of a communication failure between the two units, 
each unit will return to an autonomous operating mode until 
the fault is cleared. If the master unit is stopped due to an alarm, 
the slave unit is authorised to start.
IMPORTANT: Master/slave assembly can be congured only 
by service technicians.
8 - STANDARD CONTROL OPERATIONS AND OPTIONS
29