59 | P a g e
Compressor Stage 2 Temperature Delta
When the difference between the indoor temperature and setpoint is greater than
this value the thermostat will automatically engage compressor stage 2. This
ensures enough demand is required to engage more equipment capacity.
The default setting of 3
o
F prioritizes comfort over efficiency. When set to Auto,
the Carrier control algorithms decide when to stage, prioritizing efficiency over
comfort. In Auto, Carrier control algorithms may not engage high stage for up to
10 minutes after a manual setpoint adjustment.
Default: 3
o
F
Options: Between 1
o
F and 10
o
F or Auto
On Thermostat:
Select Menu > (hold) Service > Installation Settings > Thresholds >
Compressor Configurations > Compressor stage 2 temperature delta