To Previous Page IconTo Previous Page
Loading...
UPC Open overview and specifications
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
3
Status indicators
LED's indicate status of communications, running, errors, and power.
Environmental operating
range
-22 to 150°F (-30 to 66°C), 0 to 90% relative humidity, non-condensing
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical
Rugged GE C2950HF Cycoloy plastic
Overall dimensions
A:
B:
Mounting hole dimensions
C:
D:
E:
4-7/8 in. (12.4 cm)
2-1/20 in. (5.2 cm)
3/16 in. (.5 cm)
Panel depth
2 in. (5.1 cm)
Weight
.44 lbs (.2 kg)
BACnet support
Conforms to the BACnet Advanced Application Controller (B-AAC) Standard Device
Profile as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L,
Protocol Revision 9
Listed by
UL-916, (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15-Subpart B-Class
A
Safety considerations
WARNING Disconnect electrical power to the UPC Open before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the controller.