APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — RUN STATUS (cont)
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.
VFDS VFD INFORMATION
S.VFD
SUPPLY FAN VFD (VFD 1)
114
S.VFDSPD VFD1 Actual Speed % 0 to 100 % VFD1_SPD 114
S.VFDRPM VFD1 Actual Motor RPM 0 to 30000 VFD1RPM 114
S.VFDFREQ VFD1 Actual Motor Freq 0 to 500 VFD1FREQ 114
S.VFDAMPS VFD1 Actual Motor Amps 0 to 999 amps VFD1AMPS 114
S.VFDTORQ VFD1 Actual Motor Torque -200 to 200 % VFD1TORQ 114
S.VFDPWR VFD1 Actual Motor Power -150 to 150 kW VFD1PWR 114
S.VFDVDC VFD1 DC Bus Voltage 0 to 1000 voltage VFD1VDC 114
S.VFDV.OUT VFD1 Output Voltage 0 to 1000 voltage VFD1VOUT 114
S.VFDTEMP VFD1 Transistor Temp (C) 0 to 150 VFD1TEMP 114
S.VFDRUN.T VFD1 Cumulative Run Time 0 to 65535 hours VFD1RUNT 114
S.VFDKWH VFD1 Cumulative kWh 0 to 65535 VFD1KWH 114
S.VFDLFC VFD1 Last Fault Code 0 to 65535 VFD1LFC 114
E.VFD
EXHAUST FAN VFD (VFD 2)
E.VFDSPD VFD2 Actual Speed % 0 to 100 % VFD2_SPD 114
E.VFDRPM VFD2 Actual Motor RPM 50 to 30000 VFD2RPM 114
E.VFDFREQ VFD2 Actual Motor Freq 10 to 500 VFD2FREQ 114
E.VFDAMPS VFD2 Actual Motor Amps 0 to 999 amps VFD2AMPS 114
E.VFDTORQ VFD2 Actual Motor Torque -200 to 200 % VFD2TORQ 114
E.VFDPWR VFD2 Actual Motor Power -150 to 150 kW VFD2PWR 114
E.VFDVDC VFD2 DC Bus Voltage 0 to 1000 voltage VFD2VDC 114
E.VFDV.OUT VFD2 Output Voltage 0 to 1000 voltage VFD2VOUT 114
E.VFDTEMP VFD2 Transistor Temp (C) 0 to 150 VFD2TEMP 114
E.VFDRUN.T VFD2 Cumulative Run Time 0 to 65535 hours VFD2RUNT 114
E.VFDKWH VFD2 Cumulative kWh 0 to 65535 VFD2KWH 114
E.VFDLFC VFD2 Last Fault Code 0 to 65535 VFD2LFC 114
O.VFD
OUTDOOR FAN VFD
O.VFDSPD.A MtrMaster A Commanded % 0 to 100 % MM_A_VFD 114
O.VFDSPD.B MtrMaster B Commanded % 0 to 100 % MM_B_VFD 114
TRIP MODE TRIP HELPER
UN.C.S Unoccup. Cool Mode Start 0 to 100 dF UCCLSTRT 52,114
UN.C.E Unoccup. Cool Mode End 0 to 100 dF UCCL_END 52,114
OC.C.S Occupied Cool Mode Start 0 to 100 dF OCCLSTRT 52,114
OC.C.E Occupied Cool Mode End 0 to 100 dF OCCL_END 52,114
TEMP Ctl.Temp RAT,SPT or ZONE 0 to 100 dF CTRLTEMP
OC.H.E Occupied Heat Mode End 0 to 100 dF OCHT_END 52,114
OC.H.S Occupied Heat Mode Start 0 to 100 dF OCHTSTRT 52,114
UN.H.E Unoccup. Heat Mode End 0 to 100 dF UCHT_END 52,114
UN.H.S Unoccup. Heat Mode Start 0 to 100 dF UCHTSTRT 52,114
LINK CCN - LINKAGE
MODE Linkage Active - CCN ON/OFF MODELINK 115
L.Z.T Linkage Zone Control Tmp -40 to 240 dF LZT 115
L.C.SP Linkage Curr. Cool Setpt -40 to 240 dF LCSP 115
L.H.SP Linkage Curr. Heat Setpt -40 to 240 dF LHSP 115
HRS COMPRESSOR RUN HOURS
HR.A1 Compressor A1 Run Hours 0 to 999999 hours HOURS_A1 config 115
HR.A2 Compressor A2 Run Hours 0 to 999999 hours HOURS_A2 config 115
HR.A3 Compressor A3 Run Hours 0 to 999999 hours HOURS_A3 config 115
HR.A4 Compressor A4 Run Hours 0 to 999999 hours HOURS_A4 config 115
HR.B1 Compressor B1 Run Hours 0 to 999999 hours HOURS_B1 config 115
HR.B2 Compressor B2 Run Hours 0 to 999999 hours HOURS_B2 config 115
HR.B3 Compressor B3 Run Hours 0 to 999999 hours HOURS_B3 config 115
HR.B4 Compressor B4 Run Hours 0 to 999999 hours HOURS_B4 config 115
STRT
COMPRESSOR STARTS
ST.A1 Compressor A1 Starts 0 to 999999 CY_A1 config 115
ST.A2 Compressor A2 Starts 0 to 999999 CY_A2 config 115
ST.A3 Compressor A3 Starts 0 to 999999 CY_A3 config 115
ST.A4 Compressor A4 Starts 0 to 999999 CY_A4 config 115
ST.B1 Compressor B1 Starts 0 to 999999 CY_B1 config 115
ST.B2 Compressor B2 Starts 0 to 999999 CY_B2 config 115
ST.B3 Compressor B3 Starts 0 to 999999 CY_B3 config 115
ST.B4 Compressor B4 Starts 0 to 999999 CY_B4 config 115
VERS
SOFTWARE VERSION NUMBERS
MBB CESR131544-xx-xx string 115
RXB CESR131465-xx-xx string 115
EXB CESR131465-xx-xx string 115
CEM CESR131174-xx-xx string 115
CXB CESR131173-xx-xx string 115
SCB CESR131226-xx-xx string 115
EXV CESR131172-xx-xx string 115
EXVA CESR131172-xx-xx string 115
EXVB CESR131172-xx-xx string 115
VFD1 VERSION-313D string 115
VFD2 VERSION-313D string 115
NAVI CESR130227-xx-xx string 115