APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
* Some defaults are model number dependent.
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
E.PID EXV PID CONFIGS
EX.RR EXV PID Run Rate 5 to 120 Seconds EXV_RATE 5 49
EX.PG EXV PID Prop. Gain 0 to 5 EXV_PG 0.15 49
EX.TI EXV Integration Time 0.5 to 60 EXV_TI 12.0 49
EX.FG %EXV Move on Cir. Stg Up 0 to 100 % EXV_FF_G 15.0 49
EX.FD %EXV Move on Cir. Stg Dw 0 to 100 % EXV_FF_D 15.0 49
EX.CF EXV Pre-Move Config 0 to 3 Seconds EXVPMCFG 1 49
EX.PM EXV Pre-Move Delay Secs 0 to 30 Seconds EXVPMDLY 10 49
FL.SP EXV SH Flooding Setpoint 0 to 10 ^F FL_SP 6.0 49
FL.OV Flooding Override Pct. -10 to -1 % FL_OV -4.0 49
FL.OC Flood Ovrde Press Cutoff 0 to 1000 PSIG FL_ODPC 600.0 49
FL.OD Flooding Override Delay 0 to 255 FL_OD 0 49
EX.SL EXV Init Pos Slope -100 to 100 EXV_SLP -1.0 49
EX.IN EXV Init Pos Intercept -200 to 200 EXV_INT 110.0 49
EX.HO Hmzr Oil Ret Flood Ovrde 0 to 2 EXV_HORF 0 49
EX.SM EXV Smoothing Algorithm 0 to 1 EXV_SMAL 1 49
DP.OC DP OVERRIDE CONFIGS
DP.RS DP Rate of Change Set 2 to 15 DP_RC_ST 10 49
DP.RC DP Rate of Change Clr 0 to 5 DP_RC_CL 1 49
DP.L1 DP Override Limit 1 400 to 450 DP_OD_L1 400 49
DP.L2 DP Override Limit 2 480 to 550 DP_OD_L2 500 49
DP.TO DP Override Timeout 6 to 150 DP_OD_TO 90 49
DP.OR DP Override Percent 0 to 15 DP_OD_PT 10 49
EDT.R EVAP.DISCHRGE TEMP RESET
RS.CF
EDT Reset Configuration 0 to 3 EDRSTCFG 2 27,39,46,
48,117
RTIO Reset Ratio 0 to 10 RTIO 2 27,46, 48
LIMT Reset Limit 0 to 20 ^F LIMT 10 27,46, 48
RES.S
EDT 4-20 ma Reset Input Disable/Enable EDTRSENS Disable 27,45,46,
48
HEAT HEATING CONFIGURATION
HT.CF
Heating Control Type 0 to 5 HEATTYPE 0** 61-64,68,
69
HT.SP Heating Supply Air Setpt 65 to 120 dF SASPHEAT 85 61,62
OC.EN Occupied Heating Enabled No/Yes HTOCCENA No 61,62
LAT.M MBB Sensor Heat Relocate No/Yes HTLATMON No 61,62,68
SG.CF STAGED HEAT CONFIGS
HT.ST Modulating Gas Type 0 to 3 HTSTGTYP 0** 62,64,65
CAP.M Max Cap Change per Cycle 5 to 45 % HTCAPMAX 45** 62,64,65
M.R.DB St.Ht DB min.dF/PID Rate 0 to 5 HT_MR_DB 0.5 62,65
S.G.DB St.Heat Temp. Dead Band 0 to 5 ^F HT_SG_DB 2 62,65
RISE Heat Rise dF/sec Clamp 0.05 to 0.2 HTSGRISE 0.06 62,65
LAT.L LAT Limit Config 0 to 20 ^F HTLATLIM 10 62,65
LIM.M Limit Switch Monitoring? No/Yes HTLIMMON Yes 62,65,67
SW.H.T Limit Switch High Temp 80 to 210 dF HT_LIMHI 170** 62,65,67
SW.L.T Limit Switch Low Temp 80 to 210 dF HT_LIMLO 160** 62,65,67
HT.P Heat Control Prop. Gain 0 to 1.5 HT_PGAIN 1 62,65
HT.D Heat Control Derv. Gain 0 to 1.5 HT_DGAIN 1 62,65
HT.TM Heat PID Rate Config 30 to 300 Seconds HTSGPIDR 90 62,65
HH.CF HYDRONIC HEAT CONFIGS
HW.P Hydronic Ctl.Prop. Gain HW_PGAIN 1 62-64
HW.I Hydronic Ctl.Integ. Gain 0 to 1.5 HW_IGAIN 1 62-64
HT.D Hydronic Ctl.Derv. Gain 0 to 1.5 HW_DGAIN 1 62-64
HT.TM Hydronic PID Rate Config 15 to 300 Seconds HOTWPIDR 90 62-64
ACT.C HYDR.HEAT ACTUATOR CFGS.
SN.1 Hydronic Ht.Serial Num.1 0 to 9999 HTCL_SN1 0 62,64
SN.2 Hydronic Ht.Serial Num.2 0 to 6 HTCL_SN2 0 62,64
SN.3 Hydronic Ht.Serial Num.3 0 to 9999 HTCL_SN3 0 62,64
SN.4 Hydronic Ht.Serial Num.4 0 to 254 HTCL_SN4 0 62,64
C.A.LM Hydr.Ht.Ctl.Ang Lo Limit 0 to 90 HTCLCALM 85 62,64
SP SUPPLY STATIC PRESS.CFG.
SP.CF Static Pressure Control Disable/Enable STATICFG Disable 39,69,70
SP.SV Staged Air Volume Ctrl Disable/Enable STGAVCFG Disable 69,70
SP.S Static Pressure Sensor Disable/Enable SPSENS Disable 69,70
SP.LO Static Press. Low Range -10 to 0 SP_LOW 0 69,70
SP.HI Static Press. High Range 0 to 10 SP_HIGH 5 69,70
SP.SP
Static Pressure Setpoint 0 to 5 "H20 SPSP 1.5 27,69,70,
124
SP.MN VFD Minimum Speed 0 to 100 % STATPMIN 20 39,70
SP.MX VFD Maximum Speed 0 to 100 % STATPMAX 100 39,70
SP.FS VFD Fire Speed Override 0 to 100 % STATPFSO 100 70,82
SP.RS Stat. Pres. Reset Config 0 to 4 SPRSTCFG 0 39,45,70
SP.RT SP Reset Ratio 0 to 2 SPRRATIO 0.2 70
SP.LM SP Reset Limit 0 to 2 SPRLIMIT 0.75 70
SP.EC SP Reset Econo.Position 0 to 100 % ECONOSPR 5 70
S.PID STAT.PRESS.PID CONFIGS
SP.TM Stat.Pres.PID Run Rate 5 to 120 Seconds SPIDRATE 15 70
SP.P Static Press. Prop. Gain 0 to 5 STATP_PG 0.5 70
SP.I Static Press. Intg. Gain 0 to 2 STATP_IG 0.5 70
SP.D Static Press. Derv. Gain 0 to 5 STATP_DG 0.3 70