APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
UNIT UNIT CONFIGURATION
C.TYP Machine Control Type 1 to 4 CTRLTYPE 3 27,41,44,
50,61,88
SIZE Unit Size (75 - 150) 75 to 150 UNITSIZE 30 44,46,51
FN.MD Fan Mode (0=Auto, 1=Cont) 0 to 1 FAN_MODE 1 27,44
RM.CF Remote Switch Config 0 to 3 RMTINCFG 0 44
CEM CEM Module Installed No/Yes CEM_BRD No 44
LQ.SN Liquid Sensors Installed No/Yes LQ_SENS No 44,45
PW.MN Power Monitor Installed No/Yes PWR_MON No 44,45,125
VFD.B VFD Bypass Enable? No/Yes VFD_BYEN No 44,45
UVC.L UV-C Lamp Config? 0 to 2 UVCL_CFG 0 44,45,125
TCS.C Temp.Cmp.Strt.Cool Factr 0 to 60 Minute TCSTCOOL 0 44,45
TCS.H Temp.Cmp.Strt.Heat Factr 0 to 60 Minute TCSTHEAT 0 44,45
SFS.S Fan fail shuts down unit No/Yes SFS_SHUT No 44,45,125
SFS.M Fan Stat Monitoring Type 0 to 2 SFS_MON 0 44,45,125
VAV.S VAV Unocc.Fan Retry Time 0 to 720 Minute SAMPMINS 50 44,45
MAT.S MAT Calc Config 0 to 2 MAT_SEL 1 44,45,54
MAT.R Reset MAT Table Entries? No/Yes MATRESET No 44,45,54
MAT.D MAT Outside Air Default 0 to 100 % MATOAPOS 20 44,45
ALTI Altitude........in feet: -1000 to 60000 ALTITUDE 0 44,45
DLAY Startup Delay Time 0 to 900 DELAY 0 44,45
AUX.R Auxiliary Relay Config 0 to 3 Seconds AUXRELAY 0 44,45,46
SENS INPUT SENSOR CONFIG
SENSSPT.S Space Temp Sensor Disable/Enable SPTSENS Disable 27,44,46
SENSSP.O.S Space Temp Offset Sensor Disable/Enable SPTOSENS Disable 44,46,97
SENSSP.O.R Space Temp Offset Range 1 to 10 ^F SPTO_RNG 5 44,46,97
SENSSRH.S Space Air RH Sensor Disable/Enable SPRHSENS Disable 44,46,87
SENSRRH.S
Return Air RH Sensor Disable/Enable RARHSENS Disable 44,46,87,
123,124
SENSMRH.S Mixed Air RH Sensor Disable/Enable MARHSENS Disable 44,46,87
COOL COOLING CONFIGURATION
A1.EN Enable Compressor A1 Enable/Disable CMPA1ENA Enable 47,49
A2.EN Enable Compressor A2 Enable/Disable CMPA2ENA Enable 47,49
A3.EN Enable Compressor A3 Enable/Disable CMPA3ENA Enable 47,49
A4.EN Enable Compressor A4 Enable/Disable CMPA4ENA Enable 47,49
B1.EN Enable Compressor B1 Enable/Disable CMPB1ENA Enable 47,49
B2.EN Enable Compressor B2 Enable/Disable CMPB2ENA Enable 47,49
B3.EN Enable Compressor B3 Enable/Disable CMPB3ENA Enable 47,49
B4.EN Enable Compressor B4 Enable/Disable CMPB4ENA Enable 47,49
CS.A1 CSB A1 Feedback Alarm Enable/Disable CSB_A1EN Enable 47,49
CS.A2 CSB A2 Feedback Alarm Enable/Disable CSB_A2EN Enable 47,49
CS.A3 CSB A3 Feedback Alarm Enable/Disable CSB_A3EN Enable 47,49
CS.A4 CSB A4 Feedback Alarm Enable/Disable CSB_A4EN Enable 47,49
CS.B1 CSB B1 Feedback Alarm Enable/Disable CSB_B1EN Enable 47,49
CS.B2 CSB B2 Feedback Alarm Enable/Disable CSB_B2EN Enable 47,49
CS.B3 CSB B3 Feedback Alarm Enable/Disable CSB_B3EN Enable 47,49
CS.B4 CSB B4 Feedback Alarm Enable/Disable CSB_B4EN Enable 47,49
Z.GN Capacity Threshold Adjst 0.1 to 10.0 Z_GAIN 1 47,49,52
MC.LO Compressor Lockout Temp -25 to 55 dF OATLCOMP 40 47,49,55
LLAG Lead/Lag Configuration 0 to 2 LEAD_LAG 0 47,49
HC.EV High Capacity Evaporator No/Yes HCAPEVAP No 49
H.ODF High Efficiency OD Fans? No/Yes HIGH_EFF No 49
M.M Motor Master Control ? No/Yes MOTRMAST No 47,49,55
MM.OF MM Setpoint Offset -20 to 20 dF MMSPOFST -10.0 49
M.PID MOTORMASTER PID CONFIGS
MM.RR Motor Master PI Run Rate 5 to 120 Seconds MM_RATE 5 49
MM.PG Motor Master Prop. Gain 0 to 5 MM_PG 1.0 49
MM.PD Motor Master Deriv. Gain 0 to 5 MM_DG 0.3 49
MM.TI Motor Master Integ. Time 0.5 to 50 MM_TI 30.0 49
SCT.H Maximum Condenser Temp 100 to 150 dF SCT_MAX 115 47,49,55
SCT.L Minimum Condenser Temp 40 to 90 dF SCT_MIN 72 47,49,55
DG.A1 A1 is a Digital Scroll No/Yes DIGCMPA1 No 47,49
MC.A1 A1 Min Digital Capacity 30 to 100 % MINCAPA1 50 48,49
DS.AP Dig Scroll Adjust Delta 0 to 100 % DSADJPCT 100 48,49
DS.AD Dig Scroll Adjust Delay 15 to 60 Seconds DSADJDLY 20 48,49
DS.RP Dig Scroll Reduce Delta 0 to 100 % DSREDPCT 6 48,49
DS.RD Dig Scroll Reduce Delay 15 to 60 Seconds DSREDDLY 30 48,49
DS.RO Dig Scroll Reduction OAT 70 to 120 dF DSREDOAT 95 48,49
DS.MO Dig Scroll Max Only OAT 70 to 120 dF DSMAXOAT 105 48,49
MLV Min Load Valve Enable Disable/Enable MLV_ENAB Disable 47-49
H.SST Hi SST Alert Delay Time 5 to 30 Minutes HSSTTIME 10 48,49
RR.VF Rev Rotation Verified ? No/Yes REVR_VER No 48,49
CS.HP Use CSBs for HPS detect? No/Yes CSBHPDET Yes 49
EXV.C EXV CIRCUIT CONFIGS
EX.SA Cir. EXV Start Algorithm 0 to 1 EXV_STAL 1 49
SH.SP EXV Superheat Setpoint 5 to 40 ^F SH_SP 12.0 49
ST.SH Cir. EXV Startup SH SP 1 to 10 ^F SH_STSP 3.0 49
SH.DB EXV Superheat Deadband 0 to 2 ^F SH_DB 0.5 49
MOP.S Max Oper. Pressure SP 40 to 120 dF MOP_SP 112 49
CS.DE EXV Cir Start Delay Secs 10 to 240 Seconds EXVCSDLY 180 49
CS.PD EXV Cir PreMove Dly Secs 0 to 30 Seconds EXVCPDLY 0 49
EX.MN Comp. Cir. Exv. Min Pos% 0 to 100 % CC_XMPOS 20.0 49
EX.MC Comp Cir EXV Mn Strt Pos 0 to 100 % EXV_CSMP 40.0 49