APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — OUTPUTS
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
FANS FANS
SF.BY Supply Fan Bypass Relay Off/On SFBYRLY
S.VFD Supply Fan VFD Speed 0 to 100 % SFAN_VFD
E.VFD Exhaust Fan VFD Speed 0 to 100 % EFAN_VFD
PE.BY Power Exhaust Bypass Rly Off/On PEBYRLY
A.VFD MtrMaster A Commanded % 0 to 100 % MM_A_VFD
B.VFD MtrMaster B Commanded % 0 to 100 % MM_b_VFD
CDF.1 Condenser Fan Output 1 Off/On CONDFAN1
CDF.2 Condenser Fan Output 2 Off/On CONDFAN2
CDF.3 Condenser Fan Output 3 Off/On CONDFAN3
CDF.4 Condenser Fan Output 4 Off/On CONDFAN4
CDF.5 Condenser Fan Output 5 Off/On CONDFAN5
COOL COOLING
A1 Compressor A1 Relay Off/On CMPA1
A2 Compressor A2 Relay Off/On CMPA2
A3 Compressor A3 Relay Off/On CMPA3
A4 Compressor A4 Relay Off/On CMPA4
B1 Compressor B1 Relay Off/On CMPB1
B2 Compressor B2Relay Off/On CMPB2
B3 Compressor B3 Relay Off/On CMPB3
B4 Compressor B4 Relay Off/On CMPB4
A1.CP Compressor A1 Capacity 0 to 100 % CMPA1CAP
MLV Minimum Load Valve Relay Off/On MLV
RHV Humidimizer 3-Way Valve Off/On HUM3WVAL
C.EXV Condenser EXV Position 0 to 100 % COND_EXV
B.EXV Bypass EXV Position 0 to 100 % BYP_EXV
A1.EX Circuit A EXV 1 Position 0 to 100 % XV1APOSP
A2.EX Circuit A EXV 2 Position 0 to 100 % XV2APOSP
B1.EX Circuit B EXV 1 Position 0 to 100 % XV1BPOSP
B2.EX Circuit B EXV 2 Position 0 to 100 % XV2BPOSP
HEAT HEATING
HT.1 Heat Relay 1 Off/On HS1
H1.CP Modulating Heat Capacity 0 to 100 % HTMG_CAP
HT.2 Heat Relay 2 Off/On HS2
HT.3 Relay 3 W1 Gas Valve 2 Off/On HS3
HT.4 Relay 4 W2 Gas Valve 2 Off/On HS4
HT.5 Relay 5 W1 Gas Valve 3 Off/On HS5
HT.6 Relay 6 W2 Gas Valve 3 Off/On HS6
HT.7 Relay 7 W2 Gas Valve 4 Off/On HS7
HT.8 Relay 8 W2 Gas Valve 4 Off/On HS8
HT.9 Relay 9 W2 Gas Valve 5 Off/On HS9
HT.10 Relay 10 W2 Gas Valve 5 Off/On HS10
H.I.R Heat Interlock Relay Off/On HIR forcible
HTC.P Ht.Coil Act.Current Pos. 0 to 100 % HTCLRPOS
ACTU ACTUATORS
EC1.P Econ 1 Out Act.Curr.Pos. 0 to 100 % ECONOPOS
EC2.P Econ 2 Ret Act.Curr.Pos. 0 to 100 % ECON2POS
EC3.P Econ 3 Out Act.Curr.Pos. 0 to 100 % ECON3POS
ECN.C Econ 1 Out Act.Cmd.Pos. 0 to 100 % ECONOCMD forcible
HTC.P Ht.Coil Act.Current Pos. 0 to 100 % HTCLRPOS
HTC.C Ht.Coil Command Position 0 to 100 % HTCLCPOS
HMD.P Humidifier Act.Curr.Pos. 0 to 100 % HUMDRPOS
HMD.C Humidifier Command Pos. 0 to 100 % HUMDCPOS
GEN.O GENERAL OUTPUTS
HUM.R Humidifier Relay Off/On HUMIDRLY
UVC.L
UV-C Lamp Relay Off/On UVC_LAMP
ALRM Remote Alarm / Aux Relay Off/On ALRM forcible