APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
ECONDIAG
Economizer Active ?  No/Yes    ECACTIVE
Conditions which prevent
economizer being active:
Econ1 Out Act Unvailabl? No/Yes    ECONUNAV
Econ2 Ret Act Unvailabl? No/Yes    ECN2UNAV
Econ3 Out Act Unvailabl? No/Yes    ECN3UNAV
Enth. Switch Read High ? No/Yes    ENTH  forcible
DBC - OAT lockout?  No/Yes    DBC_STAT
DEW - OA Dewpt.lockout?  No/Yes    DEW_STAT
DDBC- OAT > RAT lockout? No/Yes    DDBCSTAT
OAEC- OA Enth Lockout?  No/Yes    OAECSTAT
DEC - Diff.Enth.Lockout? No/Yes    DEC_STAT
EDT Sensor Bad ?  No/Yes    EDT_STAT
OAT Sensor Bad ?  No/Yes    OAT_STAT
Economizer forced ?  No/Yes    ECONFORC
Supply Fan not on 30s ?  No/Yes    SFONSTAT
Cool Mode not in effect? No/Yes    COOL_OFF
OAQ lockout in effect ?  No/Yes    OAQLOCKD
Econ recovery hold off?  No/Yes    ECONHELD
Dehumid. disabled Econ.? No/Yes    DHDISABL
ECONOMZR
Econ 1 Out Act.Curr.Pos.   %  ECONOPOS
Econ 2 Ret Act.Curr.Pos.   %  ECON2POS
Econ 3 Out Act.Curr.Pos.   %  ECON3POS
Econ 1 Out Act.Cmd.Pos.    %  ECONOCMD forcible
Economizer Active ?  No/Yes    ECACTIVE
Economizer Control Point   degF  ECONCPNT
Outside Air Temperature    degF  OAT  forcible
Evaporator Discharge Tmp   degF  EDT 
Controlling Return Temp    degF  RETURN_T forcible
Econo Current Min. Pos.    %  ECMINPOS forcible
Econo Current Min. CFM    CFM  ECMINCFM
Outside Air CFM    CFM  OACFM 
GENERAL
Occupied ?  No/Yes    OCCUPIED forcible
Static Pressure    in H2O  SP  forcible
Building Pressure    in H2O  BP  forcible
Outside Air CFM    CFM  OACFM 
Return Air CFM    CFM  RACFM 
Exhaust Air CFM    CFM  EACFM 
Supply Air CFM    CFM  SACFM 
Mixed Air Rel.Humidity    %  MARH  forcible
Outside Air Rel.Humidity   %  OARH  forcible
Return Air Rel.Humidity    %  RARH  forcible
Space Relative Humidity   % SPRH forcible
Space Temperature Offset  deltaF SPTO forcible
Supply Air Setpnt. Reset   deltaF  SASPRSET forcible
Static Pressure Reset      SPRESET  forcible
IAQ - PPM Return CO2      IAQ  forcible
OAQ - PPM Return CO2      OAQ  forcible
IAQ Min.Pos. Override    %  IAQMINOV forcible
Main Filter Delta Press    in H2O  MF_DP  forcible
Main Filter Status    %  MF_STAT  forcible
Post Filter Delta Press    in H2O  PF_DP  forcible
Post Filter Status    %  PF_STAT  forcible
GENERIC
20 points dependent upon
the configuration of the
"generics" table in the
Service-Config section on page 199
HEATING
HVAC Mode..............: 16-char ASCII     
Control Mode...........: 16-char ASCII     
Heat Control Type......: 16-char ASCII     
Re-Heat Control Type...: 16-char ASCII     
Heating Mode...........: 12-char ASCII     
Requested Heat Stage      HT_STAGE
Ht.Coil Act.Current Pos.   %  HTCLRPOS
Heating Control Point    degF  HEATCPNT
Heat Relay 1  Off/On    HS1 
Modulating Heat Capacity   %  HTMG_CAP
Heat Relay 2  Off/On    HS2 
Relay 3 W1 Gas Valve 2  Off/On    HS3 
Relay 4 W2 Gas Valve 2  Off/On    HS4 
Relay 5 W1 Gas Valve 3  Off/On    HS5 
Relay 6 W2 Gas Valve 3  Off/On    HS6 
Relay 7 W1 Gas Valve 4  Off/On    HS7 
Relay 8 W2 Gas Valve 4  Off/On    HS8 
Relay 9 W1 Gas Valve 5  Off/On    HS9 
Relay 10 W2 Gas Valve 5  Off/On    HS10 
Heat Interlock Relay  Off/On    HIR  forcible