194
APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
ACTUATOR
Econ 1 Out Ser Number 1 ECN1_SN1 0
Econ 1 Out Ser Number 2 ECN1_SN2 0
Econ 1 Out Ser Number 3 ECN1_SN3 0
Econ 1 Out Ser Number 4 ECN1_SN4 0
Ecn1 Out Ctl Angl Lo Lmt ECONCALM 85
Econ 2 Ret Ser Number 1 ECN2_SN1 0
Econ 2 Ret Ser Number 2 ECN2_SN2 0
Econ 2 Ret Ser Number 3 ECN2_SN3 0
Econ 2 Ret Ser Number 4 ECN2_SN4 0
Ecn2 Ret Ctl Angl Lo Lmt ECN2CALM 85
Humd Serial Number 1 HUMD_SN1 0
Humd Serial Number 2 HUMD_SN2 0
Humd Serial Number 3 HUMD_SN3 0
Humd Serial Number 4 HUMD_SN4 0
Humd Ctrl Angle Lo Limit HUMDCALM 85
Hydronic Ht.Serial Num.1 HTCL_SN1 0
Hydronic Ht.Serial Num.2 HTCL_SN2 0
Hydronic Ht.Serial Num.3 HTCL_SN3 0
Hydronic Ht.Serial Num.4 HTCL_SN4 0
Hydr.Ht.Ctl.Ang Lo Limit HTCLCALM 85
Econ 3 Out Ser Number 1 ECN3_SN1 0
Econ 3 Out Ser Number 2 ECN3_SN2 0
Econ 3 Out Ser Number 3 ECN3_SN3 0
Econ 3 Out Ser Number 4 ECN3_SN4 0
Ecn3 Out Ctl Angl Lo Lmt ECN3CALM 85
ALLM
SPT lo alert limit/occ degF SPLO 60
SPT hi alert limit/occ degF SPHO 85
SPT lo alert limit/unocc degF SPLU 45
SPT hi alert limit/unocc degF SPHU 100
EDT lo alert limit/occ degF SALO 40
EDT hi alert limit/occ degF SAHO 100
EDT lo alert limit/unocc degF SALU 40
EDT hi alert limit/unocc degF SAHU 100
RAT lo alert limit/occ degF RALO 60
RAT hi alert limit/occ degF RAHO 90
RAT lo alert limit/unocc degF RALU 40
RAT hi alert limit/unocc degF RAHU 100
OAT low alert limit degF OATL -40
OAT high alert limit degF OATH 150
RARH low alert limit % RRHL 0
RARH high alert limit % RRHH 100
OARH low alert limit % ORHL 0
OARH high alert limit % ORHH 100
SP low alert limit in H2O SPL 0
SP high alert limit in H2O SPH 2
BP low alert limit in H2O BPL -0.25
BP high alert limit in H2O BPH 0.25
IAQ high alert limit IAQH 1200
BP__
Building Press. Config BLDG_CFG 0
Building Pressure Sensor Disable/Enable BPSENS Enable
Bldg. Press. (+/-) Range in H2O BP_RANGE 0.25
Building Pressure Setp. in H2O BPSP 0.05
BP Setpoint Offset in H2O BPSO 0.05
VFD Fire Speed % BLDGPFSO 100
VFD Minimum Speed % BLDGPMIN 10
VFD Maximum Speed % BLDGPMAX 100
Fan Track Learn Enable No/Yes DCFM_CFG No
Fan Track Learn Rate mins DCFMRATE 15
Fan Track Initial DCFM CFM DCFMSTRT 2000
Fan Track Max Clamp CFM DCFM_MAX 4000
Fan Track Max Correction CFM DCFM_ADJ 1000
Fan Track Internl EEPROM CFM DCFM_OFF 0
Fan Track Internal RAM CFM DCFM_RAM 0
Fan Track Reset Internal No/Yes DCFMRSET No
Supply Air CFM Config SCFM_CFG 2
Ret/Exh Air CFM Config RECFMCFG 2
Bldg.Pres.PID Run Rate secs BPIDRATE 10
Bldg.Press. Prop. Gain BLDGP_PG 0.5
Bldg.Press. Integ. Gain BLDGP_IG 0
Bldg.Press. Deriv. Gain BLDGP_DG Enable