APPENDIX B — CCN TABLES (cont)
SET POINT TABLE
CONFIG TABLES
SERVICE-CONFIG TABLES
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
SET_PNT
Occupied Heat Setpoint degF OHSP 68
Occupied Cool Setpoint degF OCSP 75
Unoccupied Heat Setpoint degF UHSP 55
Unoccupied Cool Setpoint degF UCSP 90
Heat-Cool Setpoint Gap deltaF HCSP_GAP 5
VAV Occ. Cool On Delta deltaF VAVOCON 3.5
VAV Occ. Cool Off Delta deltaF VAVOCOFF 2
Supply Air Setpoint degF SASP 55
Supply Air Setpoint Hi degF SASP_HI 55
Supply Air Setpoint Lo degF SASP_LO 60
Heating Supply Air Setpt degF SASPHEAT 85
Tempering Purge SASP degF TEMPPURG 50
Tempering in Cool SASP deltaF TEMPCOOL 5
Tempering Vent Occ SASP degF TEMPVOCC 65
Temper Vent Unocc. SASP degF TEMPVUNC 50
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
BRODEFS
CCN Time/Date Broadcast Off/On CCNBC Off
CCN OAT Broadcast Off/On OATBC Off
CCN OARH Broadcast Off/On OARHBC Off
CCN OAQ Broadcast Off/On OAQBC Off
Global Schedule Broadcst Off/On GSBC Off
CCN Broadcast Ack'er Off/On CCNBCACK Off
Daylight Savings Start:
Month STARTM 3
Week STARTW 2
Day STARTD 7
Minutes to Add MINADD 60
Daylight Savings Stop:
Month STOPM 11
Week STOPW 1
Day STOPD 7
Minutes to Subtract MINSUB 60
SCHEDOVR
Schedule Number SCHEDNUM 0
Accept Global Holidays? No/Yes HOLIDAYT No
Override Time Limit hours OTL 1
Timed Override Hours hours OVR_EXT 0
Accepting an Override:
SPT Override Enabled ? No/Yes SPT_OVER Yes
T58 Override Enabled ? No/Yes T58_OVER Yes
Allowed to Broadcast a
Global Sched. Override ? No/Yes GLBLOVER No
CCN Time/Date Broadcast Off/On CCNBC Off
CCN OAT Broadcast Off/On OATBC Off
CCN OARH Broadcast Off/On OARHBC Off
CCN OAQ Broadcast Off/On OAQBC Off
Global Schedule Broadcst Off/On GSBC Off
Daylight Savings Start:
Month 1 - 12 STARTM 4
Week 1 - 5 STARTW 1
Day 1 - 7 STARTD 7
Minutes to Add 0 - 90 MINADD 60
Daylight Savings Stop:
Month 1 - 12 STOPM 10
Week 1 - 5 STOPW 5
Day 1 - 7 STOPD 7
Minutes to Subtract 0 - 90 MINSUB 60
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
ACDT_CFG
EXV Superheat Deadband deltaF AC_SH_DB 2
Auto-Comp Suct.Pres Drop deltaF AC_SP_DR 3
Auto-Comp DS SP Drop deltaF AC_DS_SP 2.5
MLV/HGBP DP Drop deltaF AC_MLVDR 5
Low Charge Alert Cutoff deltaF AC_CH_LO -3
High Charge Alert Cutoff deltaF AC_CH_HI 1
Min Charge SST deltaF AC_SST_M 40