APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
ECON
Economizer Installed ? No/Yes ECON_ENA Yes
Economizer Min.Position % ECONOMIN 5
Economizer Max.Position % ECONOMAX 98
Economzr trim for sumZ ? No/Yes ECONTRIM Yes
Econ ChangeOver Select ECON_SEL 0
OA Enthalpy ChgOvr Selct OAEC_SEL 4
Outdr.Enth Compare Value OAEN_CFG 24
High OAT Lockout Temp degF OAT_LOCK 60
OA Dewpoint Temp Limit degF OADEWCFG 55
Outside Air RH Sensor Disable/Enable OARHSENS Disable
Outdoor Air CFM Sensor Disable/Enable OCFMSENS Disable
Economizer Min.Flow CFM OACFMMAX 2000
IAQ Demand Vent Min.Flow CFM OACFMMIN 0
Econ.Min.Flow Deadband CFM OACFM_DB 400
Economizer Prop.Gain EC_PGAIN 1
Economizer Range Adjust deltaF EC_RANGE 2.5
Economizer Speed Adjust EC_SPEED 0.75
Economizer Deadband deltaF EC_DBAND 0.5
Unoc Econ Free Cool Cfg UEFC_CFG 0
Unoc Econ Free Cool Time mins UEFCTIME 120
Un.Ec.Free Cool OAT Lock degF UEFCNTLO 50
Econ 1 Out Ser Number 1 ECN1_SN1 0
Econ 1 Out Ser Number 2 ECN1_SN2 0
Econ 1 Out Ser Number 3 ECN1_SN3 0
Econ 1 Out Ser Number 4 ECN1_SN4 0
Ecn1 Out Ctl Angl Lo Lmt ECONCALM 85
Econ 2 Ret Ser Number 1 ECN2_SN1 0
Econ 2 Ret Ser Number 2 ECN2_SN2 0
Econ 2 Ret Ser Number 3 ECN2_SN3 0
Econ 2 Ret Ser Number 4 ECN2_SN4 0
Ecn2 Ret Ctl Angl Lo Lmt ECN2CALM 85
Econ 3 Out Ser Number 1 ECN3_SN1 0
Econ 3 Out Ser Number 2 ECN3_SN2 0
Econ 3 Out Ser Number 3 ECN3_SN3 0
Econ 3 Out Ser Number 4 ECN3_SN4 0
Ecn3 Out Ctl Angl Lo Lmt ECN3CALM 85
EDTR
EDT Reset Configuration EDRSTCFG 0
Reset Ratio RTIO 2
Reset Limit deltaF LIMT 10
EDT 4-20 ma Reset Input Disable/Enable EDTRSENS Disable
EXVS
Cir. EXV Start Algorithm EXV_STAL 1
EXV Superheat Setpoint deltaF SH_SP 12
Cir. EXV Startup SH SP deltaF SH_STSP 3
Cir. EXV Start Pos Pct. % EXVSTPCT 80
EXV Superheat Deadband deltaF SH_DB 0.5
Max Oper. Pressure SP degF MOP_SP 112
EXV Cir Start Delay Secs secs EXVCSDLY 180
EXV Cir PreMove Dly Secs secs EXVCPDLY 0
EXV PID Run Rate secs EXV_RATE 5
EXV PID Prop. Gain EXV_PG 0.15
EXV Integration Time EXV_TI 12
EXVS_TST
EXV Pre-Move Delay Secs secs EXVPMDLY 10
EXV Pre-Move Config secs EXVPMCFG 1
%EXV Move on Cir. Stg Up % EXV_FF_G 15
%EXV Move on Cir. Stg Dw % EXV_FF_D 15
EXV SH Flooding Setpoint deltaF FL_SP 6
Flooding Override Pct. % FL_OV -4
Flood Ovrde Press Cutoff PSIG FL_ODPC 600
Flooding Override Delay FL_OD 0
EXV Init Pos Slope EXV_SLP
EXV Init Pos Intercept EXV_INT 110
Hmzr Oil Ret Flood Ovrde EXV_HORF 0
EXV Smoothing Algorithm EXV_SMAL 1
Comp. Cir. Exv. Min Pos% % CC_XMPOS 20
DP Rate of Change Set DP_RC_ST 10
DP Rate of Change Clr DP_RC_CL 1
DP Override Limit 1 DP_OD_L1 400
DP Override Limit 2 DP_OD_L2 500
DP Override Timeout DP_OD_TO 90
DP Override Percent DP_OD_PT 10