197
APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
HEAT
Heating Control Type HEATTYPE 0
Heating Supply Air Setpt degF SASPHEAT 85
Occupied Heating Enabled No/Yes HTOCCENA No
MBB Sensor Heat Relocate No/Yes HTLATMON No
Modulating Gas Type HTSTGTYP 0
Max Cap Change per Cycle % HTCAPMAX 45
St.Ht DB min.dF/PID Rate HT_MR_DB 0.5
St.Heat Temp. Dead Band deltaF HT_SG_DB 2
Heat Rise dF/sec Clamp HTSGRISE 0.06
LAT Limit Config deltaF HTLATLIM 10
Limit Switch Monitoring? No/Yes HTLIMMON Yes
Limit Switch High Temp degF HT_LIMHI 170
Limit Switch Low Temp degF HT_LIMLO 160
Heat Control Prop. Gain HT_PGAIN 1
Heat Control Derv. Gain HT_DGAIN 1
Heat PID Rate Config secs HTSGPIDR 90
Hydronic Ctl.Prop. Gain HW_PGAIN 0.7
Hydronic Ctl.Integ. Gain HW_IGAIN 0.7
Hydronic Ctl.Derv. Gain HW_DGAIN 0.5
Hydronic PID Rate Config secs HOTWPIDR 15
Hydronic Ht.Serial Num.1 HTCL_SN1 0
Hydronic Ht.Serial Num.2 HTCL_SN2 0
Hydronic Ht.Serial Num.3 HTCL_SN3 0
Hydronic Ht.Serial Num.4 HTCL_SN4 0
Hydr.Ht.Ctl.Ang Lo Limit HTCLCALM 85
HUMD
Humidifier Control Cfg. HUMD_CFG 0
Humidifier Setpoint % HUSP 40
Humidifier PID Run Rate secs HUMDRATE 30
Humidifier Prop. Gain HUMID_PG 1
Humidifier Integral Gain HUMID_IG 0.3
Humidifier Deriv. Gain HUMID_DG 0.3
Humd Serial Number 1 HUMD_SN1 0
Humd Serial Number 2 HUMD_SN2 0
Humd Serial Number 3 HUMD_SN3 0
Humd Serial Number 4 HUMD_SN4 0
Humd Ctrl Angle Lo Limit HUMDCALM 85
IAQ_
Economizer Min.Position % ECONOMIN 5
IAQ Demand Vent Min.Pos. % IAQMINP 0
Economizer Min.Flow CFM OACFMMAX 2000
IAQ Demand Vent Min.Flow CFM OACFMMIN 0
Econ.Min.Flow Deadband CFM OACFM_DB 400
IAQ Analog Sensor Config IAQANCFG 0
IAQ 4-20 ma Fan Config IAQANFAN 0
IAQ Discrete Input Confg IAQINCFG 0
IAQ Disc.In. Fan Config IAQINFAN 0
OAQ 4-20ma Sensor Config OAQANCFG 0
IAQ Econo Override Pos. % IAQOVPOS 100
IAQ Override Flow CFM IAQOVCFM 10000
Diff.Air Quality LoLimit DAQ_LOW 100
Diff.Air Quality HiLimit DAQ_HIGH 700
DAQ PPM Fan Off Setpoint DAQFNOFF 200
DAQ PPM Fan On Setpoint DAQFNON 400
Diff. AQ Responsiveness IAQREACT 0
OAQ Lockout Value OAQLOCK 0
User determined OAQ OAQ_USER 400
IAQ Low Reference IAQREFL 0
IAQ High Reference IAQREFH 2000
OAQ Low Reference OAQREFL 0
OAQ High Reference OAQREFH 2000
IAQ Purge No/Yes IAQPURGE No
IAQ Purge Duration mins IAQPTIME 15
IAQ Purge LoTemp Min Pos % IAQPLTMP 10
IAQ Purge HiTemp Min Pos % IAQPHTMP 35
IAQ Purge OAT Lockout degF IAQPNTLO 50
MM_CFG
High Efficiency OD Fans? No/Yes HIGH_EFF No
Motor Master Control ? No/Yes MOTRMAST No
Motor Master Setpoint degF MM_SP 105
MM Setpoint Offset degF MMSPOFST -10
Motor Master Deriv. Gain MM_DG 0.3
Motor Master Prop. Gain MM_PG 1
Motor Master Integ. Time MM_TI 30
Motor Master PI Run Rate secs MM_RATE 5
PROG_CFG
Liquid Sensors Installed No/Yes LQ_SENS No
Prognostics SP Enable Disable/Enable PG_SP_EN Disable
Prognostics SP Deadband in H2O PG_SP_DB 0.25
Prognostics BP Enable Disable/Enable PG_BP_EN Disable
Prognostics BP Deadband in H2O PG_BP_DB 0.05