APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
SP__
Static Pressure Control Disable/Enable STATICFG Disable
Staged Air Volume Ctrl Disable/Enable STGAVCFG Disable
Static Pressure Sensor Disable/Enable SPSENS Disable
Static Press. Low Range SP_LOW 0
Static Press. High Range SP_HIGH 5
Static Pressure Setpoint in H2O SPSP 1.5
VFD Minimum Speed % STATPMIN 20
VFD Maximum Speed % STATPMAX 100
VFD Fire Speed Override % STATPFSO 100
Stat. Pres. Reset Config SPRSTCFG 0
SP Reset Ratio SPRRATIO 0.2
SP Reset Limit SPRLIMIT 0.75
SP Reset Econo.Position % ECONOSPR 5
Stat.Pres.PID Run Rate secs SPIDRATE 15
Static Press. Prop. Gain STATP_PG 0.5
Static Press. Intg. Gain STATP_IG 0.5
Static Press. Derv. Gain STATP_DG 0.3
SWLG
Power Fault Input - Good Open/Close PWRFLOGC Close
Filter Status Inpt-Clean Open/Close FLTSLOGC Open
Post Filter Stat. In-Cln Open/Close PFLTSLGC Open
IGC Feedback - Off Open/Close GASFANLG Open
RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open
Enthalpy Input - Low Open/Close ENTHLOGC Close
Fan Status Sw. - Off Open/Close SFSLOGIC Open
Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open
Dmd.Lmt.Sw.2 - Off Open/Close DMD_SW2L Open
IAQ Disc.Input - Low Open/Close IAQINLOG Open
Fire Shutdown - Off Open/Close FSDLOGIC Open
Press. Switch - Off Open/Close PRESLOGC Open
Evacuation Sw. - Off Open/Close EVACLOGC Open
Smoke Purge Sw. - Off Open/Close PURGLOGC Open
Dehumidify Sw. - Off Open/Close DHDISCLG Open
SF Bypass Sw. - Off Open/Close SFBYLOGC Open
PE Bypass Sw. - Off Open/Close PEBYLOGC Open
TRIM
Air Temp Lvg SF Trim deltaF SAT_TRIM 0
RAT Trim deltaF RAT_TRIM 0
OAT Trim deltaF OAT_TRIM 0
SPT Trim deltaF SPT_TRIM 0
Limit Switch Trim deltaF LSW_TRIM 0
Air Tmp Lvg Evap Trim deltaF CCT_TRIM 0
A1 Discharge Temp Trim deltaF DTA1TRIM 0
Suction Gas Temp A Trim deltaF RGTATRIM 0
Cir. A EXV 1 Temp Trim deltaF CAX1TRIM 0
Cir. A EXV 2 Temp Trim deltaF CAX2TRIM 0
Cir. B EXV 1 Temp Trim deltaF CBX1TRIM 0
Cir. B EXV 2 Temp Trim deltaF CBX2TRIM 0
Suct.Press.Circ.A Trim PSI SPA_TRIM 0
Suct.Press.Circ.B Trim PSI SPB_TRIM 0
Dis.Press.Circ.A Trim PSI DPA_TRIM 0
Dis.Press.Circ.B Trim PSI DPB_TRIM 0
Bldg. Pressure Trim (ma) BPMATRIM 0
Static Press. Trim (ma) SPMATRIM 0
Outside Air CFM Trim(ma) OAMATRIM 0
Supply Air CFM Trim (ma) SAMATRIM 0
Return Air CFM Trim (ma) RAMATRIM 0
Exh. Air CFM Trim (ma) EAMATRIM 0