APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
UNIT
Machine Control Type CTRLTYPE 3
Unit Size (75 - 150) UNITSIZE 150
Fan Mode (0=auto,1=cont) FAN_MODE 0
Remote Switch Config RMTINCFG 0
CEM Module installed No/Yes CEM_BRD Yes
Liquid Sensors Installed No/Yes LQ_SENS Yes
Power Monitor Installed No/Yes PWR_MON No
VFD Bypass Enable? No/Yes VFD_BYEN No
UV-C Lamp Config? UVCL_CFG 0
Temp.Cmp.Strt.Cool Factr mins TCSTCOOL 0
Temp.Cmp.Strt.Heat Factr mins TCSTHEAT 0
Fan fail shuts down unit No/Yes SFS_SHUT Yes
Fan Stat Monitoring Type SFS_MON 0
VAV Unocc.Fan Retry Time mins SAMPMINS 50
MAT Calc Config MAT_SEL 1
Reset MAT Table Entries? No/Yes MATRESET No
MAT Outside Air Default % MATOAPOS 20
Altitude........in feet: ALTITUDE 0
Startup Delay Time secs DELAY 0
Auxiliary Relay Config AUXRELAY 0
Space Temp Sensor Disable/Enable SPTSENS Disable
Space Temp Offset Sensor Disable/Enable SPTOSENS Disable
Space Temp Offset Range deltaF SPTO_RNG 5
Space Air RH Sensor Disable/Enable SPRHSENS Enable
Return Air RH Sensor Disable/Enable RARHSENS Enable
Mixed Air RH Sensor Disable/Enable MARHSENS Disable
Main Filter Status Cfg. FLTS_ENA 0
Post Filter Status Cfg. PFLS_ENA 0
VFD_CFG
VFD1 Nominal Motor Volts volts VFD1NVLT 0
VFD1 Nominal Motor Amps amps VFD1NAMP 0
VFD1 Nominal Motor Freq VFD1NFRQ 60
VFD1 Nominal Motor RPM VFD1NRPM 1750
VFD1 Nominal Motor HPwr VFD1NPWR 0
VFD1 Motor Direction VFD1MDIR 0
VFD1 Acceleration Time secs VFD1ACCL 30
VFD1 Deceleration Time secs VFD1DECL 30
VFD1 Switching Frequency VFD1SWFQ 2
VFD1 Type VFD1TYPE 0
VFD2 Nominal Motor Volts volts VFD2NVLT 0
VFD2 Nominal Motor Amps amps VFD2NAMP 0
VFD2 Nominal Motor Freq VFD2NFRQ 60
VFD2 Nominal Motor RPM VFD2NRPM 1750
VFD2 Nominal Motor HPwr VFD2NPWR 0
VFD2 Motor Direction VFD2MDIR 0
VFD2 Acceleration Time secs VFD2ACCL 30
VFD2 Deceleration Time secs VFD2DECL 30
VFD2 Switching Frequency VFD2SWFQ 2
VFD2 Type VFD2TYPE 0
generics
Target Point Name 8-char ASCII POINT_01 SPSP
Target Point Name 8-char ASCII POINT_02 BPSP
Target Point Name 8-char ASCII POINT_03 SCT_MIN
Target Point Name 8-char ASCII POINT_04 SCT_MAX
Target Point Name 8-char ASCII POINT_05 HUSP
Target Point Name 8-char ASCII POINT_06
Target Point Name 8-char ASCII POINT_07
Target Point Name 8-char ASCII POINT_08
Target Point Name 8-char ASCII POINT_09
Target Point Name 8-char ASCII POINT_10
Target Point Name 8-char ASCII POINT_11
Target Point Name 8-char ASCII POINT_12
Target Point Name 8-char ASCII POINT_13
Target Point Name 8-char ASCII POINT_14
Target Point Name 8-char ASCII POINT_15
Target Point Name 8-char ASCII POINT_16
Target Point Name 8-char ASCII POINT_17
Target Point Name 8-char ASCII POINT_18
Target Point Name 8-char ASCII POINT_19
Target Point Name 8-char ASCII POINT_20

Table of Contents