200
APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
ACDTRSLT
Calc. Cir A Subcool Temp deltaF CSC_A
Cir A Over/Under Charge lbs AC_CHG_A
Calc. Cir B Subcool Temp deltaF CSC_B
Cir B Over/Under Charge lbs AC_CHG_B
EXV A1 Auto-Test Status AC_XA1ST
EXV A2 Auto-Test Status AC_XA2ST
EXV B1 Auto-Test Status AC_XB1ST
EXV B2 Auto-Test Status AC_XB2ST
Dig Scroll AutoTest Stat AC_DSST
MLV/HGBP AutoTest Result AC_MLVST
SF Auto-Test Result AC_SF_ST
Comp A1 Auto-Test Result AC_CP_A1
Comp A2 Auto-Test Result AC_CP_A2
Comp A3 Auto-Test Result AC_CP_A3
Comp A4 Auto-Test Result AC_CP_A4
Comp B1 Auto-Test Result AC_CP_B1
Comp B2 Auto-Test Result AC_CP_B2
Comp B3 Auto-Test Result AC_CP_B3
Comp B4 Auto-Test Result AC_CP_B4
ALARMS_1
Active Alarm 24-char ASCII ALARM_01
------------------------ 24-char ASCII
Active Alarm 24-char ASCII ALARM_02
------------------------ 24-char ASCII
Active Alarm 24-char ASCII ALARM_03
------------------------ 24-char ASCII
Active Alarm 24-char ASCII ALARM_04
------------------------ 24-char ASCII
follow same format for…
ALARMS_2 to ALARMS_5
BEL_ACTU
Econ 1 Out Act.Curr.Pos. % ECONOPOS
Econ 2 Ret Act.Curr.Pos. % ECON2POS
Econ 3 Out Act.Curr.Pos. % ECON3POS
Econ 1 Out Act.Cmd.Pos. % ECONOCMD forcible
Econ 2 Ret Act Curr Pos % ECN2RPOS
Econ 2 Ret Cmd Position % ECN2CPOS forcible
Humidifier Act.Curr.Pos. % HUMDRPOS
Humidifier Command Pos. % HUMDCPOS
Ht.Coil Act.Current Pos. % HTCLRPOS
Ht.Coil Command Position % HTCLCPOS
Econ 3 Out Act.Curr.Pos. % ECN3RPOS
Econ 3 Out Cmd Position % ECN3CPOS forcible
CIR_EXVS
Cir A EXV1 Suction Temp. degF CASTEXV1
Cir A EXV1 Superheat Tmp deltaF SH_A1
Circuit A EXV 1 Position % XV1APOSP
Cir A EXV2 Suction Temp. degF CASTEXV2
Cir A EXV2 Superheat Tmp deltaF SH_A2
Circuit A EXV 2 Position % XV2APOSP
Cir B EXV1 Suction Temp. degF CBSTEXV1
Cir B EXV1 Superheat Tmp deltaF SH_B1
Circuit B EXV 1 Position % XV1BPOSP
Cir B EXV2 Suction Temp. degF CBSTEXV2
Cir B EXV2 Superheat Tmp deltaF SH_B2
Circuit B EXV 2 Position % XV2BPOSP
Cir. EXV Start Algorithm EXV_STAL config
EXV Superheat Setpoint deltaF SH_SP config
Cir. EXV Startup SH SP deltaF SH_STSP config
Cir. EXV Start Pos Pct. % EXVSTPCT config
EXV Superheat Deadband deltaF SH_DB config
Max Oper. Pressure SP degF MOP_SP config
EXV Cir Start Delay Secs secs EXVCSDLY config
EXV Cir PreMove Dly Secs secs EXVCPDLY config
EXV PID Run Rate secs EXV_RATE config
EXV PID Prop. Gain EXV_PG config
EXV Integration Time EXV_TI config

Table of Contents